Energy | Original | D | 2/24/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2124179 |
Electrical | Original | D | 2/24/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2124178 |
Electronic Plan | Original | / | 2/24/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2124120 |
Mechanical | Original | D | 2/24/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Need constructions approval first. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2123943 |
Plumbing | Original | D | 2/24/2025 | SHANEN | SHANEN | Per plan label and code study form this is a B occupancy with an occupant load of 196. Provide an occupant load to fixture count analysis to verify compliance with section 403.1. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide the correct address on all plumbing drawings. Remove UPC reference. Elevator sump discharge piping must be shown for this phase. Mop sink with a 3" trap and drain is undersized to serve a minimum 50 gpm elevator sump discharge. All backgrounds must match per PPRBD plan review requirements. Per plan label this is a one story building and no level 2 floor plan is provided in the architectural plan set.Show all DWV and water piping serving the fixtures on level 2. Dry vent does not comply with section 905.4 as drawn. Interior finish requires all water pipe sizing, a water entry detail and a water heater installation detail. Heated water supply piping must show compliance with 2021 IECC section C404.5.1.Lavatories must show compliance with 2021 IECC section C404.5.1. Schedule L-2.Provide a water heater schedule and installation detail. Provide a piping materials schedule. Provide a water entry detail. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2123938 |
Elevators | Original | N | 2/21/2025 | ANDREAL | ANDREAL | No conveyance work being done in the scope of work. | | Elevators | 2123738 |
CO Springs Fire | Original | D | 2/19/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2122124 |
CO Springs Hazmat | Original | D | 2/19/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2122121 |
EPC Health Dept | Original | N | 2/12/2025 | HEALTHDEPT | HEALTHDEPT | Not Applicable. BR | brothrock | EPC Health Dept | 2119999 |
CO Springs DRE | Original | D | 2/11/2025 | MAMBUUL | MAMBUUL | Please upload approved development plans stamped by land use review to permit for commercial interior finish. | | CO Springs DRE | 2119801 |
CSU Contract Admin. | Original | N | 2/10/2025 | CSUAPPSPRM | CSUAPPSPRM | No fees due this plan set.BS | bschifferstein | CSU Contract Admin. | 2119270 |
Gas/Elec. Utils | Original | N | 2/10/2025 | CSUREVIEW | CSUREVIEW | No apparent conflicts. DMM | dmakings | Gas/Elec. Utils | 2119226 |
CSU Waste Water | Original | N | 2/10/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2119222 |
CSU Water | Original | N | 2/10/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2119220 |
Zoning/Planning | Original | / | 2/10/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2119055 |
City Engr | Original | N | 2/10/2025 | HVO | HVO | | | City Engr | 2119038 |
Construction | Original | D | 2/10/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, code data, listed assemblies. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2118974 |
Electronic Plan | Original | / | 2/6/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2118002 |
Floodplain | Original | N | 1/31/2025 | AMY | AMY | | | Floodplain | 2116086 |
Enumeration | Original | A | 1/31/2025 | AMY | AMY | This will be suite 100 | | Enumeration | 2116084 |
Electronic Plan | Original | / | 1/31/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2116065 |
Energy | Original | / | 1/31/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2115811 |
Floodplain | Original | / | 1/31/2025 | RBD GIS | RBD GIS | Autogenerated Review: Floodplain status unknown. (Parcel: 6220403121) | | Floodplain | 2115810 |