CSU Water | Original | A | 6/26/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | CSU Water | 2177282 |
CO Springs Fire | Original | A | 6/26/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2177147 |
Energy | Original | D | 6/26/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2176912 |
Plumbing | Original | D | 6/26/2025 | SHANEN | SHANEN | Review stopped and incomplete. Provide sheet P100. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2176911 |
Zoning/Planning | Original | / | 6/25/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2176837 |
| Original | / | 6/25/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2176828 |
| Original | / | 6/25/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2176771 |
Submittal 6 | Original | / | 6/25/2025 | SIERRAC | SIERRAC | Submittal #6 - Phased Commercial C (thru Core and Shell) | | Submittal 6 | 2176770 |
CO Springs Fire | Original | D | 6/24/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | michael.davis1@color | CO Springs Fire | 2176022 |
CO Springs DRE | Original | D | 6/16/2025 | SSADLER | SSADLER | Previous comments not addressed. The documents uploaded are the approved development plan not the final recorded plat.
These plans have reached the maximum allotted plan reviews, and a re-review fee has been assessed. Fees must be paid prior to further reviews. To pay fees for permit review please follow the link provided. https://aca-prod.accela.com/COSPRINGS/Default.aspx
Click on “Building” tab and enter record number BLDREV 25-00530 or enter required information in fields provided. | | CO Springs DRE | 2172289 |
Zoning/Planning | Original | / | 6/11/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2170364 |
Plumbing | Original | D | 6/11/2025 | SHANEN | SHANEN | Remove ALL references to the mechanical scope from the plumbing plans. Plumbing plans and mechanical plans must be submitted separately. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2170142 |
Energy | Original | D | 6/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2170143 |
CSU Water | Original | D | 6/11/2025 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2170059 |
| Original | / | 6/11/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2170056 |
| Original | / | 6/11/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2170021 |
Submittal 5 | Original | / | 6/11/2025 | QUINTONW | QUINTONW | Submittal #5 - Phased Commercial C (thru Core and Shell) | | Submittal 5 | 2170020 |
CO Springs DRE | Original | D | 6/11/2025 | SSADLER | SSADLER | Upload the final recorded plat. All other requirements are uploaded. | | CO Springs DRE | 2169838 |
CO Springs Fire | Original | D | 6/4/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2166917 |
CSU Water | Original | D | 5/28/2025 | CSUREVIEW | CSUREVIEW | See previous comments. Re-review after addressing the Plumbing comments. MDA | malcuran | CSU Water | 2163838 |
City Engr | Original | A | 5/27/2025 | JDAGNILLO | JDAGNILLO | | | City Engr | 2163093 |
Energy | Original | D | 5/27/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2162903 |
Plumbing | Original | D | 5/27/2025 | SHANEN | SHANEN | P100: All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. Show piping for WH-1. Show waste and vent piping for FS-1. Clarify how a floor sink serving a water meter and discharging to the grease waste is in compliance with section 1003.2. All piping subject to freezing conditions must show compliance with section 305.4. P200: See clouded notes 8 and 4. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2162902 |
Zoning/Planning | Original | / | 5/27/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2162868 |
| Original | / | 5/27/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2162850 |
| Original | / | 5/27/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2162843 |
Submittal 4 | Original | / | 5/27/2025 | BECKYA | BECKYA | Submittal #4 - Phased Commercial C (thru Core and Shell) | | Submittal 4 | 2162842 |
CO Springs Fire | Original | D | 5/20/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2160594 |
CO Springs DRE | Original | D | 5/14/2025 | SSADLER | SSADLER | Previous comments not addressed. Upload the final recorded plat. Financial assurances for all private improvements must be posted prior to building permit release.
These plans have reached the maximum allotted plan reviews, and a re-review fee has been assessed. Fees must be paid prior to further reviews. To pay fees for permit review please follow the link provided. https://aca-prod.accela.com/COSPRINGS/Default.aspx
Click on “Building” tab and enter record number BLDREV 25-00530 or enter required information in fields provided. | | CO Springs DRE | 2158427 |
Energy | Original | D | 5/12/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2157456 |
Mechanical | Original | A | 5/12/2025 | DALEH | DALEH | | | Mechanical | 2157455 |
City Engr | Original | D | 5/9/2025 | HVO | HVO | Please see previous comment- include a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan | | City Engr | 2157299 |
CSU Water | Original | D | 5/9/2025 | CSUREVIEW | CSUREVIEW | See previous comments. Re-review after addressing the Plumbing comments. CSFD made a comment related to the FH that needs to be ADDRESSED ON THE Utility Service Plan. mjg | mgackle | CSU Water | 2157191 |
Zoning/Planning | Original | / | 5/9/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2157126 |
Plumbing | Original | D | 5/9/2025 | SHANEN | SHANEN | P100: Provide a piping materials schedule. Water service and water entry location shall comply with CSU (Colorado Springs Utilities) water line extension and service standards. See water line extension and service standards at CSU.org. All piping subject to freezing conditions must show compliance with section 305.4. Show compliance with section 608.15.2.1. If wall hydrant and water service is to be installed at this phase, the piping for the wall hydrant must be shown and compliance with section 305.4 must be clarified as the mechanical plans indicate this core and shell will be unconditioned. If the BFP is to be installed at this phase, compliance with section 305.4 and 608.15.2.1 is required. P200: See clouded notes 8 and 4. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2157096 |
| Original | / | 5/9/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2157067 |
| Original | / | 5/9/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2156739 |
Submittal 3 | Original | / | 5/9/2025 | SIERRAC | SIERRAC | Submittal #3 - Phased Commercial C (thru Core and Shell) | | Submittal 3 | 2156738 |
CO Springs Fire | Original | D | 4/28/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2151137 |
CO Springs DRE | Original | D | 4/22/2025 | SSADLER | SSADLER | Previous items not corrected. Upload the final recorded plat. All private financial assurances must be posted prior to building permit release. | | CO Springs DRE | 2148572 |
Electrical | Original | A | 4/21/2025 | BERTHA | BERTHA | | | Electrical | 2148292 |
Energy | Original | D | 4/21/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2148293 |
Electronic Plan | Original | / | 4/21/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2148133 |
City Engr | Original | D | 4/18/2025 | JDAGNILLO | JDAGNILLO | Include a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. (Project Dox #STM-REV25-0021) | | City Engr | 2147680 |
Mechanical | Original | D | 4/18/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2147633 |
Plumbing | Original | D | 4/17/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide a piping materials schedule. Water service and water entry location shall comply with CSU (Colorado Springs Utilities) water line extension and service standards. See water line extension and service standards at CSU.org. All piping subject to freezing conditions must show compliance with section 305.4. Show compliance with section 608.15.2.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2147387 |
Zoning/Planning | Original | / | 4/17/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2147384 |
CSU Water | Original | D | 4/17/2025 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. MLW | mlwilliams | CSU Water | 2147379 |
CSU Waste Water | Original | A | 4/17/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. MLW | mlwilliams | CSU Waste Water | 2147377 |
Construction | Original | A | 4/17/2025 | JUSTINL | JUSTINL | Approved for core shell phase only. Trusses pending. | | Construction | 2147365 |
Electronic Plan | Original | / | 4/17/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2147361 |
Enumeration | Original | A | 4/14/2025 | AMY | AMY | | | Enumeration | 2144634 |
Electronic Plan | Original | / | 4/14/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2144628 |
Submittal 2 | Original | / | 4/14/2025 | QUINTONW | QUINTONW | Submittal #2 - Phased Commercial C (thru Core and Shell) | | Submittal 2 | 2144589 |
CO Springs DRE | Original | D | 3/28/2025 | CHUDSPETH | CHUDSPETH | Plans have been denied until planner review is complete. All CDI fees were paid on 3/28/2025 | | CO Springs DRE | 2137968 |
CSU Contract Admin. | Original | A | 3/25/2025 | CSUAPPSPRM | CSUAPPSPRM | Utility Charges and Fees paid. BS | bschifferstein | CSU Contract Admin. | 2135775 |
CSU Contract Admin. | Original | / | 3/25/2025 | CSUAPPSPRM | CSUAPPSPRM | | bschifferstein | CSU Contract Admin. | 2135774 |
CO Springs Hazmat | Original | N | 3/21/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2134580 |
CO Springs Fire | Original | D | 3/21/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2134578 |
Energy | Original | D | 3/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2132937 |
Electrical | Original | D | 3/18/2025 | BERTHA | BERTHA | Provide location of Panel A.
Comply with 110.26(D)
Provide conductor size, type and quantity
Alternates are not allowed. Information must be verified at time of plan submittal.
Provide available fault current and withstand rating for Panel A * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2132936 |
Electronic Plan | Original | / | 3/18/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2132904 |
Mechanical | Original | N | 3/18/2025 | DALEH | DALEH | | | Mechanical | 2132752 |
Elevators | Original | N | 3/17/2025 | ANDREAL | ANDREAL | No Conveyance in the Thru Core and Shell scope of work. | | Elevators | 2132237 |
CSU Contract Admin. | Original | D | 3/13/2025 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form (CWMSF) approved. However paid utility receipt for applicable Development Charges/Fees are required. Contact Customer Contract Administration at 719-668-8111 for any questions. BS | bschifferstein | CSU Contract Admin. | 2131021 |
CO Springs DRE | Original | D | 3/12/2025 | MAMBUUL | MAMBUUL | 1. Need to upload recorded plat to permit. 2. Need to pay CDI fees per approval letter from land use review, PDZD-24-0029, please contact DREplanninginfo@coloradosprings.gov to pay fees. 3. Need to provide financial assurances for public and private improvements prior to building permit approval. | | CO Springs DRE | 2130332 |
EPC Health Dept | Original | N | 3/12/2025 | HEALTHDEPT | HEALTHDEPT | Approved for foundation, core and shell only.
Retail food establishment plan review will be required with interior finish submittal. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2130081 |
CSU Water | Original | D | 3/11/2025 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
The water entry location on the plumbing plans does not match the water entry location on the approved Utility Service Plan (USP). The plumbing plans must match the USP. CJS | cjsavage | CSU Water | 2129690 |
Gas/Elec. Utils | Original | A | 3/11/2025 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. CJS | cjsavage | Gas/Elec. Utils | 2129688 |
CSU Waste Water | Original | D | 3/11/2025 | CSUREVIEW | CSUREVIEW | Sanitary service exit locations and Grease Interceptor location on the plumbing plan do not match the approved Utility Service Plan (USP). The plumbing plan and USP must match. CJS | cjsavage | CSU Waste Water | 2129687 |
City Engr | Original | D | 3/11/2025 | HVO | HVO | Please include a signed copy of the approved Grading & Erosion Control Plan from the Stormwater Enterprise. | | City Engr | 2129556 |
CSU Contract Admin. | Original | D | 3/11/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2129537 |
Zoning/Planning | Original | / | 3/11/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2129459 |
Construction | Original | D | 3/11/2025 | JUSTINL | JUSTINL | See code data on architectural and structural sheets. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2129423 |
Energy | Original | / | 3/11/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2129386 |
Plumbing | Original | D | 3/11/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. Building drain locations do not match the CSU approved USP. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Water service and water entry location shall comply with CSU (Colorado Springs Utilities) water line extension and service standards. See water line extension and service standards at CSU.org. All piping subject to freezing conditions must show compliance with section 305.4. Show compliance with section 608.15.2.1. Provide gpm and/or square footage served by each component of the roof drainage system. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2129214 |
Electronic Plan | Original | / | 3/10/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2129141 |
Enumeration | Original | A | 3/3/2025 | AMY | AMY | 1 PLAN 2 PERMITS REQUIRED. Trash enclosure address is 101 Spectrum Loop. | | Enumeration | 2126469 |
Electronic Plan | Original | / | 3/3/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2126467 |
Energy | Original | N | 3/3/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2126263 |
Floodplain | Original | N | 3/3/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6207100017) | | Floodplain | 2126262 |