Energy | Original | D | 5/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2156163 |
Mechanical | Original | D | 5/8/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Provide stamped engineering letter regarding roof system's ability to withstand weight of new equipment. Provide structural plan containing all required code data if necessary. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2156162 |
Electrical | Original | D | 5/6/2025 | BERTHA | BERTHA | Clarify demolition vs new.
Provide Rated Input Current for VFDs - comply with 430.122 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2154830 |
Electronic Plan | Original | / | 5/6/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2154827 |
Plumbing | Original | D | 5/5/2025 | SHANEN | SHANEN | P001: Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Reference current code cycles throughout. P111: Water heaters are scheduled on sheet P600. See redlines. P600: Provide section C404.2 efficiency requirements. See redlines. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2154506 |
Elevators | Original | N | 5/5/2025 | ROBERTV | ROBERTV | No work being done to existing conveyance | | Elevators | 2154489 |
CO Springs DRE | Original | A | 5/2/2025 | CVANAPPLEDORN | CVANAPPLEDORN | Commercial interior remodel. No change of use or occupancy. | | CO Springs DRE | 2154180 |
CO Springs Hazmat | Original | N | 5/2/2025 | CSFIRE | CSFIRE | No inspection | michael.davis1@color | CO Springs Hazmat | 2153628 |
CO Springs Fire | Original | N | 5/2/2025 | CSFIRE | CSFIRE | No fire inspection | michael.davis1@color | CO Springs Fire | 2153627 |
Zoning/Planning | Original | / | 5/2/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2153579 |
CSU Water | Original | N | 5/1/2025 | CSUREVIEW | CSUREVIEW | No plumbing scope of work. mjg | mgackle | CSU Water | 2153337 |
CSU Waste Water | Original | N | 5/1/2025 | CSUREVIEW | CSUREVIEW | No plumbing scope of work. mjg | mgackle | CSU Waste Water | 2153336 |
Construction | Original | D | 5/1/2025 | BPHILLIPS | BPHILLIPS | Provide stamped engineering letter regarding roof system's ability to withstand weight of new equipment. Provide structural plan containing all required code data if necessary. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2153321 |
Electronic Plan | Original | / | 5/1/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2153136 |
Floodplain | Original | N | 4/30/2025 | KEITH | KEITH | | | Floodplain | 2152652 |
Enumeration | Original | D | 4/30/2025 | BRENT | BRENT | This plan was submitted as 729 E. Las Vegas and the plan pages show that address, but, the code study form shows the address of 701 E. Las Vegas St. What is the correct address? The vicinity map is not clear enough to determine the location of the scope of work. Include a better site plan showing the buildings on the parcel with addressing and the area of work highlighted. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2152565 |
Electronic Plan | Original | / | 4/30/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2152558 |
Energy | Original | / | 3/17/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2132228 |
Floodplain | Original | / | 3/17/2025 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6420301020) | | Floodplain | 2132227 |