Falcon Fire (CSFD) | Original | N | 6/3/2025 | CSFIRE | CSFIRE | No Fire Inspection | michael.davis1@color | Falcon Fire (CSFD) | 2166425 |
Falcon Fire (CSFD) | Original | / | 6/3/2025 | CSFIRE | CSFIRE | | michael.davis1@color | Falcon Fire (CSFD) | 2166424 |
Electrical | Original | A | 6/3/2025 | BERTHA | BERTHA | | | Electrical | 2165841 |
Electronic Plan | Original | / | 6/3/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2165837 |
Falcon Hazmat (CSFD) | Original | N | 6/2/2025 | CSFIRE | CSFIRE | Below Permit Quantity of 70 kWh. only 38kWh. FDMUS | mark.stanwood@colora | Falcon Hazmat (CSFD) | 2165680 |
Falcon Hazmat (CSFD) | Original | D | 6/2/2025 | CSFIRE | CSFIRE | See Fire Comments | michael.davis1@color | Falcon Hazmat (CSFD) | 2165322 |
Falcon Fire (CSFD) | Original | D | 6/2/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | Falcon Fire (CSFD) | 2165321 |
| Original | / | 5/22/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2162194 |
| Original | / | 5/22/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2162190 |
Submittal 3 | Original | / | 5/22/2025 | SIERRAC | SIERRAC | Submittal #3 | | Submittal 3 | 2162189 |
County Zoning | Original | A | 5/21/2025 | DSDMATHY2 | DSDMATHY2 | | | County Zoning | 2161530 |
Falcon Fire (CSFD) | Original | D | 5/2/2025 | CSFIRE | CSFIRE | Battery type/technology must be specified. Provide Chemical inventory list with total amount of battery electrolytes
Provide completed Hazardous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility. Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2021 IFC Table 105.5.22. PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS AND FILL OUT THE REQUESTED INFORMATION. All forms and packets are available at https://coloradosprings.gov/hazmat | chiptaylor | Falcon Fire (CSFD) | 2153895 |
Falcon Hazmat (CSFD) | Original | D | 5/2/2025 | CSFIRE | CSFIRE | | chiptaylor | Falcon Hazmat (CSFD) | 2153893 |
Electrical | Original | D | 4/29/2025 | BERTHA | BERTHA | Comply with previous review comment - provide electrical site plan. Indicate location of all electrical equipment - SSC and Battery Cabinet. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2151931 |
Electronic Plan | Original | / | 4/29/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2151663 |
Submittal 2 | Original | / | 4/25/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2150522 |
County Zoning | Original | D | 4/18/2025 | DSDMATHY2 | DSDMATHY2 | Conditions of Approval tied to this project: 1. Approval of TWR257 is contingent on compliance with PPRBD and Falcon Fire review comments. 2. Applicant is to finalize co-location lease agreement prior to installation.
Please provide an updated lease agreement that is signed to the Planner who approved TWR257. Once this is done, this can be approved. | | County Zoning | 2147772 |
Falcon Fire (CSFD) | Original | D | 4/16/2025 | CSFIRE | CSFIRE | (DISAPPROVED) HAZARDOUS MATERIALS
Provide electrolyte capacity in gallons for proposed batteries
Provide completed Hazardous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility. Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2021 IFC Table 105.5.22. PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS AND FILL OUT THE REQUESTED INFORMATION. All forms and packets are available at https://coloradosprings.gov/hazmat | Jacob.Watson | Falcon Fire (CSFD) | 2146596 |
Falcon Hazmat (CSFD) | Original | D | 4/16/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | Falcon Hazmat (CSFD) | 2146593 |
Electrical | Original | D | 4/8/2025 | BERTHA | BERTHA | remove all alternates. complete re-review of one-line required
provide electrical site plan. indicate location of all electrical equipment. this plan must be part of the electrical plan set.
provide available fault current and withstand rating for electrical equipment.
provide panel schedules with volt amps on all circuits and calculated load of panel in amps * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2141908 |
Electronic Plan | Original | / | 4/8/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2141881 |
Mechanical | Original | N | 4/3/2025 | TREVORH | TREVORH | Not Applicable; no mechanical scope. | | Mechanical | 2140211 |
Zoning/Planning | Original | / | 4/2/2025 | DSDMATHY2 | DSDMATHY2 | In Current Review by DSDMATHY2 | | Zoning/Planning | 2139838 |
Plumbing | Original | N | 4/2/2025 | SHANEN | SHANEN | | | Plumbing | 2139773 |
Construction | Original | N | 4/2/2025 | SHELLEY | SHELLEY | No new construction scope, existing monopine. | | Construction | 2139663 |
Electronic Plan | Original | / | 4/2/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2139643 |
Enumeration | Original | A | 4/2/2025 | BRENT | BRENT | | | Enumeration | 2139484 |
Electronic Plan | Original | / | 4/2/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2139473 |
Water Division | Original | / | 4/1/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2138935 |
Waste Water Div | Original | / | 4/1/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2138936 |
Floodplain | Original | N | 4/1/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5136401040) | | Floodplain | 2138934 |