Fountain Fire | Original | D | 6/3/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | Fountain Fire | 2166446 |
Energy | Original | D | 5/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2164561 |
Plumbing | Original | D | 5/29/2025 | SHANEN | SHANEN | Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. Meter/BFP size does not match civil plans. Alternate materials and methods application form fee must be paid prior to processing. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2164560 |
Construction | Original | A | 5/29/2025 | JUSTINL | JUSTINL | | | Construction | 2164490 |
Enumeration | Original | A | 5/27/2025 | BRENT | BRENT | | | Enumeration | 2163389 |
Electronic Plan | Original | / | 5/27/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2163386 |
| Original | / | 5/27/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2163325 |
| Original | / | 5/27/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2163232 |
Submittal 3 | Original | / | 5/27/2025 | SHELLEY | SHELLEY | Submittal #3 | | Submittal 3 | 2163231 |
Fountain Fire | Original | D | 5/20/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | michael.davis1@color | Fountain Fire | 2160965 |
Energy | Original | D | 5/15/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2159196 |
Mechanical | Original | A | 5/15/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2159195 |
Electrical | Original | A | 5/15/2025 | RICHG | RICHG | | | Electrical | 2159042 |
EPC Health Dept | Original | N | 5/14/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1606 is valid from 05/15/2025 - 11/15/2025. To continue any earthmoving operations after 11/15/2025, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2158780 |
Plumbing | Original | D | 5/14/2025 | SHANEN | SHANEN | Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. Clarify why HW increases in size downstream. Meter/BFP size does not match civil plans. EWC-1 does not comply with section 410.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2158752 |
Construction | Original | D | 5/14/2025 | JUSTINL | JUSTINL | Commercial IECC form showing insulation values and additional energy efficiency options not provided with resubmitted plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2158732 |
Electronic Plan | Original | / | 5/14/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2158661 |
Enumeration | Original | A | 5/14/2025 | BRENT | BRENT | | | Enumeration | 2158615 |
Electronic Plan | Original | / | 5/14/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2158603 |
Submittal 2 | Original | / | 5/13/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2158351 |
Fountain Water | Original | A | 5/13/2025 | FOUNTAIN | FOUNTAIN | Applicable Water Tap Fees Paid 5/13/2025 | TMurphy | Fountain Water | 2158268 |
Fountain Zoning | Original | A | 5/13/2025 | ZONINGF | ZONINGF | OK to release for permitting. Use tax 25-037F. KM | KMartinez | Fountain Zoning | 2158267 |
Fountain Waste Water | Original | A | 5/13/2025 | FNTNSAN | FNTNSAN | | Jmoore3431 | Fountain Waste Water | 2158239 |
Fountain Water | Original | D | 5/7/2025 | FOUNTAIN | FOUNTAIN | Payment of Water Tap Fee required before plans can be approved by Fountain Water | TMurphy | Fountain Water | 2155568 |
Fountain Waste Water | Original | D | 5/7/2025 | FNTNSAN | FNTNSAN | Applicant needs to pay their sanitary sewer tap fee, before plans can be approved by FSD. Please contact Jonathan Moore at 719-382-5303 | Jmoore3431 | Fountain Waste Water | 2155530 |
Fountain Fire | Original | D | 4/22/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | Fountain Fire | 2148820 |
Fountain Hazmat | Original | N | 4/22/2025 | CSFIRE | CSFIRE | | chiptaylor | Fountain Hazmat | 2148817 |
Energy | Original | D | 4/21/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2148376 |
Electrical | Original | D | 4/21/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2148375 |
Electronic Plan | Original | / | 4/21/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2148320 |
Mechanical | Original | D | 4/17/2025 | TCRIPPEN | TCRIPPEN | Disapproved need construction first see construction notes * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2147476 |
Plumbing | Original | D | 4/17/2025 | SHANEN | SHANEN | Construction review comments regarding occupancy and occupant load must be addressed to verify compliance with section 403.1. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Water service and meter sizing does not match referenced civil plans. Water heater detail must show compliance with 2021 IECC section 404.3. All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. ET-1 is for residential use only per manufacturer. EWC-1 does not comply with section 410.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2147435 |
Elevators | Original | N | 4/17/2025 | ANDREAL | ANDREAL | No Conveyance in this scope of work. | | Elevators | 2147254 |
EPC Health Dept | Original | D | 4/11/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2143654 |
Construction | Original | D | 4/10/2025 | JUSTINL | JUSTINL | See life safety plan, enlarged floor plan, IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2143442 |
Energy | Original | / | 4/10/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2143289 |
Electronic Plan | Original | / | 4/8/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2142107 |
Enumeration | Original | A | 4/3/2025 | BRENT | BRENT | | | Enumeration | 2140570 |
Electronic Plan | Original | / | 4/3/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2140542 |
Waste Water Div | Original | / | 4/3/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2140366 |
Zoning/Planning | Original | / | 4/3/2025 | SYSTEM | SYSTEM | You will need to contact Zoning/Planning department for approval prior to permit. This department will not review the plan electronically. | | Zoning/Planning | 2140367 |
Water Division | Original | / | 4/3/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2140365 |
Energy | Original | / | 4/3/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2140364 |
Floodplain | Original | N | 4/3/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5530008016) | | Floodplain | 2140363 |