CO Springs Fire | Original | A | 5/14/2025 | CSFIRE | CSFIRE | You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | phil.valdez | CO Springs Fire | 2158671 |
CO Springs Hazmat | Original | N | 5/14/2025 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2158658 |
Mechanical | Original | D | 5/8/2025 | TCRIPPEN | TCRIPPEN | Disapproved pending construction comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2156143 |
CO Springs DRE | Original | A | 5/7/2025 | KDODGE | KDODGE | interior remodel, no change in use. Reconfigure 1st and 2nd floor offices, cubicles, break room, conference room. | | CO Springs DRE | 2155485 |
Electrical | Original | D | 5/7/2025 | BERTHA | BERTHA | Provide complete one-line, include all conductor size, type and quantity starting with the utility transformer through the scope of work.
Provide site plan / overall floor plan - indicate the location of electrical meters, disconnects, and panels clearly identified as new or existing
Provide fault current information (SCCR, AIC, SCA) in tabular form at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Clarify New vs Existing.
Comply with C405.11 - 2021 IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2155368 |
Electronic Plan | Original | / | 5/6/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2155080 |
Plumbing | Original | D | 5/6/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All condensate and gas piping related items must be on the mechanical plans. Remove all references to condensate and gas piping from he plumbing plans. The slope of horizontal drainage piping shall comply with section 704. Clarify how removal of the drinking fountain is in compliance with section 403.1 and 410. Clarify plumbing scope in secure construction area sheet notes. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2154856 |
Zoning/Planning | Original | / | 5/5/2025 | KDODGE | KDODGE | In Current Review by KDODGE | | Zoning/Planning | 2154781 |
CSU Water | Original | N | 5/5/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. CJS | cjsavage | CSU Water | 2154773 |
CSU Waste Water | Original | N | 5/5/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. CJS | cjsavage | CSU Waste Water | 2154770 |
Construction | Original | D | 5/5/2025 | JUSTINL | JUSTINL | See code references, life safety plans, floor plans * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2154659 |
Energy | Original | N | 5/5/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2154428 |
Electronic Plan | Original | / | 5/2/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2153759 |
Enumeration | Original | N | 4/30/2025 | AMY | AMY | | | Enumeration | 2152748 |
Electronic Plan | Original | / | 4/30/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2152677 |
Energy | Original | / | 4/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2147731 |
Floodplain | Original | N | 4/18/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7327101001) | | Floodplain | 2147730 |