Tri-Lakes Fire (CSFD) | Original | D | 5/6/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | Tri-Lakes Fire (CSFD) | 2154950 |
Tri-Lakes Hazmat (CSFD) | Original | D | 5/6/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | Tri-Lakes Hazmat (CSFD) | 2154945 |
Monument Zoning | Original | D | 5/2/2025 | TOWNOFMON | TOWNOFMON | | bholtztom | Monument Zoning | 2153794 |
Monument Water | Original | D | 5/2/2025 | TOWNOFMON | TOWNOFMON | | bholtztom | Monument Water | 2153793 |
Electrical | Original | D | 4/29/2025 | BERTHA | BERTHA | Provide available fault current and withstand rating for ATS and all new air conditioning / refrigeration equipment.
Comply with C405.11 in all applicable areas - printer/copier, break room, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2152144 |
Energy | Original | D | 4/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2152145 |
Electronic Plan | Original | / | 4/29/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2152130 |
Energy | Original | / | 4/29/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2152072 |
Mechanical | Original | D | 4/25/2025 | TREVORH | TREVORH | Disapproved; Construction review comments regarding occupant load must be addressed to verify compliance * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2150850 |
Plumbing | Original | D | 4/25/2025 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. Provide a piping insulation materials schedule, code references are not an acceptable substitute. EWC-1 does not comply with section 410.3. ST-5 is for residential use only per manufacturer. Provide a DWV isometric drawing. Water service entry location does not referenced civil drawings. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2150739 |
Elevators | Original | N | 4/25/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2150718 |
EPC Health Dept | Original | N | 4/25/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. KB. | KBauer | EPC Health Dept | 2150657 |
Construction | Original | D | 4/25/2025 | BPHILLIPS | BPHILLIPS | Occupancy types, occupant load, LSP. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2150606 |
Electronic Plan | Original | / | 4/23/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2149840 |
Enumeration | Original | A | 4/22/2025 | AMY | AMY | | | Enumeration | 2148854 |
Electronic Plan | Original | / | 4/22/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2148851 |
Waste Water Div | Original | / | 4/21/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2148333 |
Energy | Original | / | 4/21/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2148332 |
Floodplain | Original | N | 4/21/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7111306006) | | Floodplain | 2148331 |