CO Springs DRE | Original | D | 6/20/2025 | MAMBUUL | MAMBUUL | Previous comments not addressed. Please upload approved development plans stamped by land use review to permit for commercial interior finish. | | CO Springs DRE | 2174637 |
Zoning/Planning | Original | / | 6/20/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2174636 |
Electrical | Original | D | 6/16/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2172010 |
EPC Health Dept | Original | D | 6/16/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1611 is valid from 05/09/2025 - 11/09/2025. To continue any earthmoving operations after 11/09/2025, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/.
Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly.
For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2171918 |
Mechanical | Original | D | 6/16/2025 | TCRIPPEN | TCRIPPEN | Disapproved: Missing hood specs and hood pages for hood C * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2171896 |
Zoning/Planning | Original | / | 6/16/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2171866 |
CSU Water | Original | A | 6/16/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | CSU Water | 2171819 |
Plumbing | Original | D | 6/16/2025 | SHANEN | SHANEN | P-000: Grease waste piping shall comply with section 704.1. Remove ALL references to gas piping from the plumbing plans. P-001: Provide manufacturer model number for MS-1. P-002: Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. P-301: Note 3 not shown on referenced sheet. Missing symbols and notes throughout. Lavatories must show compliance with 2021 IECC section C404.5.1. P-401: Piping insulation schedule must include materials and manufacturer. P-403: Water heater detail must show compliance with 2021 IECC section 404.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2171813 |
Construction | Original | A | 6/16/2025 | SHELLEY | SHELLEY | | | Construction | 2171740 |
Enumeration | Original | A | 6/12/2025 | BECKYA | BECKYA | | | Enumeration | 2171037 |
Submittal 2 | Original | / | 6/12/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2170854 |
Mechanical | Original | D | 5/19/2025 | TCRIPPEN | TCRIPPEN | Disapproved: See selection 507.1 Exception #1 must comply with all . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2160008 |
Electronic Plan | Original | / | 5/14/2025 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 2158673 |
CO Springs Fire | Original | D | 5/13/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2158012 |
CO Springs Hazmat | Original | D | 5/13/2025 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2158011 |
EPC Health Dept | Original | D | 5/12/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1611 is valid from 05/09/2025 - 11/09/2025. To continue any earthmoving operations after 11/09/2025, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/.
Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly.
For questions, contact Environmental Health at 719-578-3199 option 3. | tguerrero | EPC Health Dept | 2157539 |
Plumbing | Original | D | 5/7/2025 | SHANEN | SHANEN | P-000: Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See highlighted sections on clouded additional requirements for 2021 IECC block. All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. P-001: Provide manufacturer model number for MS-1. P-002: Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. P-200: All plumbing fixtures in a restaurant, except restroom fixtures, water entry floor drain, ice machine and waste receptors for condensate, must discharge to the grease waste. Notes 17 and 19 missing from under floor plan. See notes 6 and 7. Waste receptors must comply with section 802.4. Grease waste piping shall comply with section 704.1. P-301: Clouded notes are missing or incorrect. See clouds. Provide notes 26 and up. Lavatories must show compliance with 2021 IECC section C404.5.1. Water heater detail must show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. P-401: Piping insulation schedule must include materials and manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2155373 |
Electrical | Original | D | 5/6/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2155164 |
Electronic Plan | Original | / | 5/6/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2155145 |
Elevators | Original | N | 5/6/2025 | ANDREAL | ANDREAL | No Conveyance in this scope of work. | | Elevators | 2155137 |
CO Springs DRE | Original | D | 5/2/2025 | MAMBUUL | MAMBUUL | Please upload approved development plans stamped by land use review to permit for commercial interior finish. | | CO Springs DRE | 2154094 |
City Engr | Original | N | 5/2/2025 | JDAGNILLO | JDAGNILLO | | | City Engr | 2153999 |
CSU Contract Admin. | Original | N | 5/2/2025 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees due this plan set. CWMSF has already approved and all fees paid. BS | bschifferstein | CSU Contract Admin. | 2153831 |
EPC Health Dept | Original | D | 5/2/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1546 has expired as of 04/30/2025. To continue earthmoving operations, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3.
Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to healthinfo@elpasoco.com. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2153788 |
Zoning/Planning | Original | / | 5/2/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2153672 |
CSU Water | Original | D | 5/2/2025 | CSUREVIEW | CSUREVIEW | Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. MLW | mlwilliams | CSU Water | 2153537 |
CSU Waste Water | Original | A | 5/2/2025 | CSUREVIEW | CSUREVIEW | Refer to core and shell permit for approved development plan and approved utility construction drawings. MLW | mlwilliams | CSU Waste Water | 2153536 |
Gas/Elec. Utils | Original | A | 5/2/2025 | CSUREVIEW | CSUREVIEW | Refer to core and shell permit for approved development plan and approved utility construction drawings. ------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. MLW | mlwilliams | Gas/Elec. Utils | 2153535 |
Zoning/Planning | Original | / | 5/1/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2153495 |
Construction | Original | D | 5/1/2025 | BRIANB | BRIANB | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2153459 |
Energy | Original | N | 4/29/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2152085 |
Electronic Plan | Original | / | 4/24/2025 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2150259 |
Enumeration | Original | D | 4/23/2025 | BECKYA | BECKYA | Remove dumpster enclosure plans from Arch plans. These have already been reviewed under the Core and Shell Plan. Additionally, include an Architectural Site Plan in the Architectural Plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2149302 |
Electronic Plan | Original | / | 4/23/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2149283 |
Energy | Original | / | 4/22/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2148882 |
Floodplain | Original | N | 4/22/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6207301004) | | Floodplain | 2148881 |