Energy | Original | D | 6/17/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2173045 |
Electrical | Original | A | 6/17/2025 | BERTHA | BERTHA | | | Electrical | 2173044 |
County Zoning | Original | D | 6/17/2025 | DSDBENSON2 | DSDBENSON2 | Plat (VR239) has not yet been recorded. Site Development Plan (PPR2336) has not yet been approved. | | County Zoning | 2172726 |
Electronic Plan | Original | / | 6/16/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2172144 |
Mechanical | Original | A | 6/16/2025 | TCRIPPEN | TCRIPPEN | Approved: | | Mechanical | 2172065 |
EPC Health Dept | Original | N | 6/16/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1617 is valid from 07/01/2025 - 01/01/2026. To continue any earthmoving operations after 01/01/2026, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2171921 |
Plumbing | Original | D | 6/16/2025 | SHANEN | SHANEN | Remove ALL references to the mechanical scope from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2171700 |
Enumeration | Original | D | 6/16/2025 | AMY | AMY | The El Paso County Assessor’s database should read that existing lots 11690 & 11750 Owl Place are vacate land, if these structures has been removed. Since a wrecking permit is not required to have a manufactured home removed with RBD. Please contact the El Paso County Assessor’s office once these structures are removed, so that this can be verified and their database reflects this.
The approval of this plan is pending the review of the mylar (pre-plat), plat fees being collected and a copy of the final recorded plat received by this department. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2171651 |
Electronic Plan | Original | / | 6/16/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2171644 |
Construction | Original | A | 6/13/2025 | DOUGC | DOUGC | | | Construction | 2171275 |
Electronic Plan | Original | / | 6/13/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2171249 |
Submittal 2 | Original | / | 6/12/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2170961 |
Falcon Hazmat (CSFD) | Original | N | 5/13/2025 | CSFIRE | CSFIRE | | phil.valdez | Falcon Hazmat (CSFD) | 2158007 |
Falcon Fire (CSFD) | Original | D | 5/13/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | Falcon Fire (CSFD) | 2158006 |
Energy | Original | D | 5/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2156618 |
Mechanical | Original | D | 5/8/2025 | TCRIPPEN | TCRIPPEN | Disapproved pending construction and IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2156617 |
County Zoning | Original | D | 5/7/2025 | DSDBENSON2 | DSDBENSON2 | Plat (VR239) has not yet been recorded. Site Development Plan (PPR2336) has not yet been approved. | | County Zoning | 2155933 |
EPC Health Dept | Original | D | 5/7/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. BR | brothrock | EPC Health Dept | 2155906 |
Plumbing | Original | D | 5/7/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See highlighted sections on clouded additional requirements for 2021 IECC block. Enumeration comments must be addressed. Remove all references to the mechanical scope from the plumbing plans. All gas piping related items shall be on the mechanical plans. Remove all references to gas piping from the plumbing plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2155727 |
Electrical | Original | D | 5/7/2025 | BERTHA | BERTHA | Remove parallel neutral - remove SSBJ from service conductor.
Comply with C405.11 - 2021 IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2155378 |
Electronic Plan | Original | / | 5/7/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2155369 |
Elevators | Original | N | 5/6/2025 | ANDREAL | ANDREAL | No Conveyance in this scope of work. | | Elevators | 2155186 |
Zoning/Planning | Original | / | 5/2/2025 | DSDBENSON2 | DSDBENSON2 | In Current Review by DSDBENSON2 | | Zoning/Planning | 2153859 |
Construction | Original | D | 5/2/2025 | DOUGC | DOUGC | IECC // Soils Report * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2153805 |
Electronic Plan | Original | / | 5/1/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2153161 |
Enumeration | Original | D | 4/25/2025 | AMY | AMY | As stated in the review of this project with El Paso County Development Services, the Enumerations department commented, if the office is attached to a storage building the address would be 7939 but if it is not attached the address would be 7945 Meridian Park Drive. Since the building is detached there would not be a letter associated with this building address. 7939 was crossed out on all sheets. 7945 was added to most sheets. If any of the sheets that were corrected get changed out, correct the address to 7945 Meridian Park Drive.
The El Paso County Assessor’s database should read that existing lots 11690 & 11750 Owl Place are vacate land, if these structures has been removed. Since a wrecking permit is not required to have a manufactured home removed with RBD. Please contact the El Paso County Assessor’s office once these structures are removed, so that this can be verified and their database reflects this.
On page A0.03 label the street name in the street.
The approval of this plan is pending the review of the mylar (pre-plat), plat fees being collected and a copy of the final recorded plat received by this department. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2150678 |
Electronic Plan | Original | / | 4/25/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2150571 |
Water Division | Original | / | 4/24/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2150158 |
Waste Water Div | Original | / | 4/24/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2150159 |
Energy | Original | / | 4/24/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2150157 |
Floodplain | Original | N | 4/24/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5301001001) | | Floodplain | 2150156 |