| Original | / | 7/17/2025 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2185997 |
Submittal 3 | Original | / | 7/17/2025 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2185996 |
Energy | Original | D | 7/10/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2182487 |
Mechanical | Original | A | 7/10/2025 | DALEH | DALEH | | | Mechanical | 2182486 |
CO Springs DRE | Original | A | 7/9/2025 | CVANAPPLEDORN | CVANAPPLEDORN | Previous CO Springs DRE approval comment still applies. | | CO Springs DRE | 2182242 |
Zoning/Planning | Original | / | 7/8/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2181400 |
Electrical | Original | D | 7/8/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2181383 |
Submittal 2 | Original | / | 7/8/2025 | SIERRAC | SIERRAC | Submittal #2 | | Submittal 2 | 2181316 |
CO Springs DRE | Original | A | 5/29/2025 | KDODGE | KDODGE | interior remodel, no change in use. replace cooling systems and electrical equipment. | | CO Springs DRE | 2164539 |
Zoning/Planning | Original | / | 5/29/2025 | KDODGE | KDODGE | In Current Review by KDODGE | | Zoning/Planning | 2164538 |
CO Springs Hazmat | Original | N | 5/28/2025 | CSFIRE | CSFIRE | NO INSPECTION | michael.davis1@color | CO Springs Hazmat | 2163422 |
CO Springs Fire | Original | N | 5/28/2025 | CSFIRE | CSFIRE | NO FIRE INSPECTION | michael.davis1@color | CO Springs Fire | 2163421 |
Zoning/Planning | Original | / | 5/27/2025 | CVANAPPLEDORN | CVANAPPLEDORN | In Current Review by CVANAPPLEDORN | | Zoning/Planning | 2163343 |
CSU Waste Water | Original | N | 5/27/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2163063 |
CSU Water | Original | N | 5/27/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2163062 |
Energy | Original | D | 5/27/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2162962 |
Mechanical | Original | D | 5/27/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2162961 |
Electrical | Original | D | 5/27/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2162954 |
Electronic Plan | Original | / | 5/27/2025 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2162943 |
Electronic Plan | Original | / | 5/27/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2162899 |
Plumbing | Original | N | 5/27/2025 | SHANEN | SHANEN | | | Plumbing | 2162884 |
Enumeration | Original | N | 5/27/2025 | BECKYA | BECKYA | | | Enumeration | 2162840 |
Electronic Plan | Original | / | 5/27/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2162837 |
Energy | Original | / | 5/8/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2156070 |
Floodplain | Original | N | 5/8/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418203012) | | Floodplain | 2156068 |