CO Springs Fire | Original | D | 6/13/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2171431 |
CO Springs Hazmat | Original | D | 6/13/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2171430 |
EPC Health Dept | Original | D | 6/4/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | EPC Health Dept | 2167099 |
Energy | Original | D | 6/4/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2166642 |
Mechanical | Original | D | 6/4/2025 | TREVORH | TREVORH | Disapproved; will this maintenance building be used to service gas vehicles or to charge electric golf style maintenance carts? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2166641 |
Gas/Elec. Utils | Original | A | 6/4/2025 | CSUREVIEW | CSUREVIEW | No apparent conflicts. DMM | dmakings | Gas/Elec. Utils | 2166523 |
CSU Waste Water | Original | D | 6/4/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2166522 |
CSU Water | Original | D | 6/4/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2166521 |
Plumbing | Original | D | 6/3/2025 | SHANEN | SHANEN | All gas and condensate piping related items shall be on the mechanical plans.Remove all references to gas and condensate piping from the plumbing plans. Provide a piping insulation materials schedule, code tables are not an acceptable substitute. Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. See highlighted sections on clouded additional requirements for 2021 IECC block. Water heater detail must show compliance with 2021 IECC section 404.3 and 2021 IPC section 504.2. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Show meter/BFP assembly and provide a water entry detail. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2166318 |
Electrical | Original | A | 6/3/2025 | DANIELG | DANIELG | | | Electrical | 2166256 |
Elevators | Original | N | 6/3/2025 | ROBERTV | ROBERTV | No Conveyances - NOTE: This is one of many plans for Bradley Ridge Apartments | | Elevators | 2166247 |
CO Springs DRE | Original | D | 6/3/2025 | MAMBUUL | MAMBUUL | 1. Please upload recorded plat to permit. Final plat appears to be in review with land use review. 2. Please upload final landscape and irrigation plan set stamped by land use review to permit. 3. Need to pay CDI and PLDO fees per approval letter DEPN-24-0134, please contact DREplanninginfo@coloradosprings.gov to pay fees. 4. Need to provide financial assurances for public and private improvements prior to building permit approval. | | CO Springs DRE | 2166196 |
Zoning/Planning | Original | / | 6/3/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2166188 |
City Engr | Original | D | 6/3/2025 | HVO | HVO | Please provide a signed copy of the approved Grading & Erosion Control Plan and Permanent Control Measures from the Stormwater Enterprise (if applicable). | | City Engr | 2166160 |
CSU Contract Admin. | Original | D | 6/3/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form (CWMSF) and payment of development charges/fees. CWMSF available at https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf. Contact Customer Contract Administration at 719-668-8111 for more information. BS | bschifferstein | CSU Contract Admin. | 2166152 |
Construction | Original | D | 6/3/2025 | BRIANB | BRIANB | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2166111 |
Electronic Plan | Original | / | 5/30/2025 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2164933 |
Enumeration | Original | D | 5/30/2025 | AMY | AMY | The approval of this plan is pending the review of the mylar(replat), collecting the plat fees and a copy of the final recorded plat.
The trash enclosure should not be shown in multiple plan submittals. This structure will not need to be permitted with RBD. Remove or cross out. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2164847 |
Electronic Plan | Original | / | 5/30/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2164832 |
Energy | Original | / | 5/14/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2158669 |
Floodplain | Original | N | 5/14/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5500000513) | | Floodplain | 2158668 |