CO Springs Fire | Original | D | 6/13/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2171092 |
CO Springs Hazmat | Original | D | 6/13/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2171091 |
Energy | Original | D | 6/5/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2167513 |
Mechanical | Original | D | 6/5/2025 | TCRIPPEN | TCRIPPEN | Disapproved Pending construction and rated walls? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2167512 |
City Engr | Original | A | 6/4/2025 | HVO | HVO | EDRD has no comments. | | City Engr | 2166967 |
Electrical | Original | D | 6/3/2025 | BERTHA | BERTHA | Provide compliance with 230.70(A)(1)
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2166465 |
CSU Waste Water | Original | D | 6/3/2025 | CSUREVIEW | CSUREVIEW | Utility Service Plan (USP) provides a 6" sanitary service stub. The plumb plans (P1.1) show a 4" service exiting the building. Provide clarity on either the USP or plumbing plans as to where the 6"x4" reducer will be located, inside or outside the building. CJS | cjsavage | CSU Waste Water | 2166107 |
CSU Water | Original | D | 6/3/2025 | CSUREVIEW | CSUREVIEW | Requires approval of the Commercial Water Meter Sizing Form.
Plumbing sheet P5.0: Meter detail provides conflicting information. 4" riser reduces to 3" at the 90° bend, then continues as 3" to a 2" meter. Per detail B1-6 the meter loop will reduce to 2" via a threaded tap on the 3" blind flange right after the 90° bend. Remove non-standard meter entry detail and replace with the applicable CSU standard detail. CJS | cjsavage | CSU Water | 2166092 |
Gas/Elec. Utils | Original | A | 6/3/2025 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. CJS | cjsavage | Gas/Elec. Utils | 2166078 |
EPC Health Dept | Original | D | 6/3/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT1272 has expired as of 08/20/23. To continue earthmoving operations, please reapply for a new permit online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/.
New retail food establishment plan review required (not approved by BR in 2023). Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | EPC Health Dept | 2166046 |
Plumbing | Original | D | 6/3/2025 | SHANEN | SHANEN | P0.1: Piping insulation material schedule must include material (fiberglass, elastomeric foam, etc.) and manufacturer. P4.0: SH-1 and SH-2 appear to be mislabeled per fixture schedule. Clarify. Controls and hand showers shall comply with ICC A117.1-2017 section 608.4. P6.0: SH-1 and SH-2 appear to be mislabeled on sheet P4.0. Clarify. Water heater schedule must show efficiency requirements are met per section C404.2. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2165908 |
CSU Contract Admin. | Original | D | 6/3/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF was attached, but requires more information.
AMS | ASweet | CSU Contract Admin. | 2165877 |
Electronic Plan | Original | / | 6/3/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2165862 |
Elevators | Original | N | 6/2/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2165816 |
CO Springs DRE | Original | D | 6/2/2025 | MAMBUUL | MAMBUUL | 1. Please upload recorded plat to permit. 2. Need to provide financial assurances for public and private improvements prior to building permit approval. No CDI fees due per approval letter. | | CO Springs DRE | 2165722 |
Zoning/Planning | Original | / | 6/2/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2165682 |
Construction | Original | D | 6/2/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, wood in IIB construction. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2165677 |
Electronic Plan | Original | / | 5/29/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2164125 |
Enumeration | Original | D | 5/22/2025 | BRENT | BRENT | Include a detailed site plan in the Architectural plan pages. Show the elevations for the trash enclosure in the architectural plan pages. Trash enclosures over 7 feet in height will require a separate address and building permit. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2162333 |
Electronic Plan | Original | / | 5/22/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2162302 |
Energy | Original | / | 5/22/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2161987 |
Floodplain | Original | N | 5/22/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220201035) | | Floodplain | 2161986 |