CO Springs Fire | Original | A | 7/15/2025 | CSFIRE | CSFIRE | Site Safety Plan per IFC 3301.1 required within 45 days of permit issuance.
You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | chiptaylor | CO Springs Fire | 2184250 |
Electronic Plan | Original | / | 7/11/2025 | RICHG | RICHG | In Current Review by RICHG | | Electronic Plan | 2183284 |
CO Springs DRE | Original | D | 7/10/2025 | SSADLER | SSADLER | Previous comments not addressed. Upload the final recorded plat. CDI fees are due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov Financial assurances for all private improvements must be posted prior to building permit issuance. | | CO Springs DRE | 2182398 |
City Engr | Original | A | 7/7/2025 | HVO | HVO | EDRD has no additional comments. | | City Engr | 2180565 |
Zoning/Planning | Original | / | 7/7/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2180432 |
Plumbing | Original | A | 7/7/2025 | SHANEN | SHANEN | | | Plumbing | 2180429 |
Mechanical | Original | A | 7/3/2025 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2180408 |
CSU Water | Original | A | 7/3/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Water | 2180387 |
CSU Waste Water | Original | A | 7/3/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. mjg | mgackle | CSU Waste Water | 2180386 |
Gas/Elec. Utils | Original | A | 7/3/2025 | CSUREVIEW | CSUREVIEW | Comments addressed. CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2180385 |
Construction | Original | A | 7/3/2025 | DOUGC | DOUGC | | | Construction | 2180366 |
Electronic Plan | Original | / | 7/3/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2180360 |
Enumeration | Original | A | 7/3/2025 | BRENT | BRENT | Plan now showing as single tenant building. | | Enumeration | 2180171 |
Electronic Plan | Original | / | 7/3/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2180163 |
Submittal 2 | Original | / | 7/3/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2180097 |
CSU Contract Admin. | Original | A | 6/13/2025 | CSUAPPSPRM | CSUAPPSPRM | Utility Charges and Fees paid 06/13/2025 JMD | jdemello | CSU Contract Admin. | 2171543 |
CSU Contract Admin. | Original | / | 6/13/2025 | CSUAPPSPRM | CSUAPPSPRM | | jdemello | CSU Contract Admin. | 2171542 |
CO Springs Fire | Original | D | 6/13/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2171423 |
CO Springs Hazmat | Original | N | 6/13/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2171422 |
Energy | Original | D | 6/12/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2170847 |
Electrical | Original | D | 6/12/2025 | BERTHA | BERTHA | Verify compliance with 210.25(B) Comply with 250.122(G) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2170846 |
Gas/Elec. Utils | Original | D | 6/4/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | Gas/Elec. Utils | 2166518 |
CSU Waste Water | Original | D | 6/4/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2166517 |
CSU Water | Original | D | 6/4/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2166516 |
Electronic Plan | Original | / | 6/4/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2166504 |
CSU Contract Admin. | Original | D | 6/3/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires Approved Commercial Water Meter Sizing Form and Paid Utility Receipt - JMD | jdemello | CSU Contract Admin. | 2166456 |
Mechanical | Original | D | 6/3/2025 | TCRIPPEN | TCRIPPEN | Disapproved see the IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2166359 |
Plumbing | Original | D | 6/3/2025 | SHANEN | SHANEN | Provide roof plumbing plan to show location, piping and sizing for roof primary/overflow drains and overflow scuppers. Provide gpm and/or square footage served by components of the roof drain system. Schedule roof drains. Clarify how water service will comply with section 305.4 as mechanical plans do not indicate a heat source. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2166331 |
City Engr | Original | D | 6/3/2025 | HVO | HVO | Please include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2166252 |
Elevators | Original | N | 6/3/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2166249 |
CO Springs DRE | Original | D | 6/3/2025 | MAMBUUL | MAMBUUL | 1. Need to upload approved development plans stamped by land use review to permit. Plans are currently in review with land use review. 2. Please upload recorded plat to permit. 3. Please upload final landscaping and irrigation plan sets stamped by land use review to permit. 4. Upon issuance of approval letter CDI fees may be due. Once approval letter is issued please contact DREplanninginfo@coloradosprings.gov to pay fees. 5. Need to provide financial assurance for public and private improvements prior to building permit approval. | | CO Springs DRE | 2166099 |
Zoning/Planning | Original | / | 6/3/2025 | MAMBUUL | MAMBUUL | In Current Review by MAMBUUL | | Zoning/Planning | 2166082 |
EPC Health Dept | Original | N | 6/3/2025 | HEALTHDEPT | HEALTHDEPT | Approved for core and shell only.
Retail food establishment plan review will be required with interior finish submittal. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please email application and all required documents to heaenvironmental@elpasoco.com.
For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | EPC Health Dept | 2166080 |
Construction | Original | D | 6/3/2025 | DOUGC | DOUGC | See Architectural plan and IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2166001 |
Energy | Original | / | 6/2/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2165827 |
Electronic Plan | Original | / | 6/2/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2165778 |
Enumeration | Original | D | 5/30/2025 | BRENT | BRENT | The secondary addressing shown on pages A001 and A101 does not follow the RBD secondary addressing guidelines available on our website. Update to show secondary addressing which is compliant with these guidlelines. The tax schedule number shown on the code study form is incorrect. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2165067 |
Electronic Plan | Original | / | 5/30/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2165036 |
Energy | Original | / | 5/28/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2163566 |
Floodplain | Original | N | 5/28/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5331202032) | | Floodplain | 2163565 |