CO Springs DRE | Original | A | 6/20/2025 | MAMBUUL | MAMBUUL | Approved for commercial interior/exterior remodel for minor interior and exterior modifications. No change to use. Pre-application summary uploaded to permit. | | CO Springs DRE | 2174671 |
Energy | Original | D | 6/18/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2173154 |
Mechanical | Original | D | 6/18/2025 | TCRIPPEN | TCRIPPEN | Disapproved :IMC 2021 section 603.8 603.8.1,603.8.2,- Ducts shall be sealed prior to concrete en casement or direct burial. Ducts shall be leak tested as required by Section C403 of the International Energy Conservation Code. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2173153 |
Electrical | Original | A | 6/17/2025 | DANIELG | DANIELG | | | Electrical | 2172761 |
Electronic Plan | Original | / | 6/17/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2172737 |
Plumbing | Original | D | 6/17/2025 | SHANEN | SHANEN | Include all plumbing fixtures (urinals) in water calculations and re-calculate totals. Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. Provide a water heater detail to show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. Provide detail for water heater platform construction or schedule manufactured platform. See highlighted sections on clouded additional requirements for 2021 IECC block. 3/4" is undersized to serve downstream fixtures (9.5 wsfu max). Show water piping to the urinals. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2172379 |
Zoning/Planning | Original | / | 6/16/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2172280 |
CSU Waste Water | Original | N | 6/16/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2172094 |
CSU Water | Original | N | 6/16/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2172093 |
Construction | Original | D | 6/16/2025 | SHELLEY | SHELLEY | Provide complete life safety plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2172077 |
Energy | Original | / | 6/16/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2172072 |
Electronic Plan | Original | / | 6/16/2025 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2171925 |
Enumeration | Original | N | 6/16/2025 | BRENT | BRENT | | | Enumeration | 2171768 |
Electronic Plan | Original | / | 6/16/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2171741 |
Energy | Original | / | 6/6/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2168146 |
Floodplain | Original | N | 6/6/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7424105010) | | Floodplain | 2168145 |