Energy | Original | D | 6/20/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2174420 |
Electrical | Original | D | 6/20/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2174419 |
Electronic Plan | Original | / | 6/20/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2174403 |
Mechanical | Original | D | 6/19/2025 | TREVORH | TREVORH | Disapproved; does Roll up door comply with the 2021 IECC section 402.5.11 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2174194 |
Plumbing | Original | D | 6/19/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide roof plumbing plan to show location, piping and sizing for roof primary/overflow drains and overflow scuppers. Provide gpm and/or square footage served by components of the roof drain system. Schedule roof drains. All gas piping and condensate piping related items shall be on the mechanical plans. Remove all references to gas piping and condensate piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. See highlighted sections on clouded additional requirements for 2021 IECC block. Yard hydrant must be provided with a separate backflow preventer per section 608.8. Lavatories must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2173865 |
Elevators | Original | N | 6/18/2025 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2173730 |
EPC Health Dept | Original | N | 6/18/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. BR | brothrock | EPC Health Dept | 2173292 |
Construction | Original | D | 6/18/2025 | BPHILLIPS | BPHILLIPS | site plan, clear floor space, snow exposure * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2173233 |
Electronic Plan | Original | / | 6/18/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2173091 |
Enumeration | Original | D | 6/17/2025 | BECKYA | BECKYA | Please provide an Architectural Site Plan in the Architectural Plans. Enumerations does not approve Civil or Development plans for permit. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2172486 |
Waste Water Div | Original | / | 6/16/2025 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2171846 |
Water Division | Original | / | 6/16/2025 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2171845 |
Energy | Original | / | 6/16/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2171844 |
Floodplain | Original | N | 6/16/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5530008019) | | Floodplain | 2171843 |