CO Springs Fire | Original | D | 7/14/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2183864 |
CO Springs Hazmat | Original | D | 7/14/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2183863 |
CO Springs DRE | Original | D | 7/3/2025 | SSADLER | SSADLER | Upload the approved stamped development plan including the final landscaping and irrigation plans. Upload the approval letter. Upload the final recorded plat. Financial assurances for all private improvements must be posted. CDI fees may be due. | | CO Springs DRE | 2180314 |
Electrical | Original | D | 7/1/2025 | BERTHA | BERTHA | Provide all conductor size, type and quantity.
Remove parallel neutral - no ground in service conductor.
Provide series rated listed combinations.
Comply with C405.11 - 2021 IECC
Provide fault current information for new air conditioning and refrigeration equipment. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2178910 |
City Engr | Original | D | 7/1/2025 | HVO | HVO | Please include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2178775 |
Electronic Plan | Original | / | 7/1/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2178691 |
Mechanical | Original | D | 7/1/2025 | DALEH | DALEH | Label floor plans with room names Remove equipment from floor plan that is located on roof Provide a roof plan and indicate roof access Show complete condensate routing and size Show complete gas pipe routing and size, If located on roof show on roof plan Installation of a washer box as shown in Plumbing schedule requires a dryer vent to exterior Comcheck must be stamped, signed and dated by design professional See plans for complete comments that need to be addressed on the plan sheets Response letters are not a sole means of approval * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2178688 |
Plumbing | Original | D | 7/1/2025 | SHANEN | SHANEN | CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. All condensate piping related items shall be on the mechanical plans. Remove ALL references to condensate piping from the plumbing plans. All gas piping related items shall be on the mechanical plans Remove ALL references to gas piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove ALL references to UPC. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2178665 |
CSU Contract Admin. | Original | D | 6/30/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires Commercial Water Meter Sizing Form (https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf) and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111 for more information. JMD | jdemello | CSU Contract Admin. | 2178486 |
CSU Water | Original | D | 6/30/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
DMMRefer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. | dmakings | CSU Water | 2178451 |
CSU Waste Water | Original | D | 6/30/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2178450 |
Gas/Elec. Utils | Original | D | 6/30/2025 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | Gas/Elec. Utils | 2178449 |
Zoning/Planning | Original | / | 6/30/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2178434 |
Construction | Original | D | 6/30/2025 | BPHILLIPS | BPHILLIPS | Code study form, IECC/ Comcheck, occupancy type * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2178421 |
Electronic Plan | Original | / | 6/27/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2177685 |
Enumeration | Original | D | 6/27/2025 | AMY | AMY | 1 PLAN 5 PERMITS REQUIRED. 3008 S Academy Blvd that is shown on the Code Study form and on all other sheets of this plan. 3008 has nothing to do with this project. This is an existing lot to remain. Correct the address on all sheets.
A Code Study form is required for the pay station, add the address of 3004 S Academy Blvd to this Code Study form.
The existing Code Study form will have 3002, 3006, 3010, 3010 ½ S Academy Blvd. See Enumerations comments to the City Planning department regarding addressing.
In page A1.01 the street name should be spelled HANCOCK NOT Hankcock. Addressing has been added to this sheet. If this sheet gets changed out, add the addresses back to this sheet as shown.
The address to the 8ft trash enclosure is 3010 ½ S Academy Blvd.
A wrecking permit is required to be in place prior to Enumerations approving this plan. Approval of this plan is pending in the Enumerations department is for the review the mylar prior to plat, collection of plat fees and a copy of the final recorded plat and the above items. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2177618 |
Electronic Plan | Original | / | 6/27/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2177517 |
Floodplain | Original | N | 6/26/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6434408002) | | Floodplain | 2176951 |