CO Springs Fire | Original | D | 8/11/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2195714 |
CO Springs Hazmat | Original | N | 8/11/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2195713 |
CO Springs DRE | Original | D | 8/5/2025 | SSADLER | SSADLER | Upload the approved and stamped development plan. | | CO Springs DRE | 2193850 |
Electrical | Original | D | 8/5/2025 | BERTHA | BERTHA | Provide conduit/conductor size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work.
Provide fault current information (SCCR, AIC, SCA) in tabular form at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide footprint (site plan) showing all electrical service equipment and disconnects serving the structure
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior)
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Controlled receptacles must be shown on the plan per C405.11 and the symbol used to mark these receptacles must be as shown in article 406.3(E) of the adopted National Electrical Code (NEC).
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2193523 |
Electronic Plan | Original | / | 8/5/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2193421 |
EPC Health Dept | Original | N | 8/1/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. Existing leased space for new retail store. MT | mtemple | EPC Health Dept | 2192718 |
Mechanical | Original | D | 8/1/2025 | TCRIPPEN | TCRIPPEN | Pending IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2192212 |
Zoning/Planning | Original | / | 8/1/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2192169 |
CSU Water | Original | N | 7/31/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | CSU Water | 2192094 |
CSU Waste Water | Original | N | 7/31/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 2192093 |
Mechanical | Original | / | 7/31/2025 | JANE | JANE | Overtime approved for Mechanical by Michelle Slayden | | Mechanical | 2192057 |
Electrical | Original | / | 7/31/2025 | JANE | JANE | Overtime approved for Electrical by Michelle Slayden | | Electrical | 2192056 |
Plumbing | Original | D | 7/31/2025 | SHANEN | SHANEN | Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provide a piping materials schedule. Provide project address on all plumbing drawings. All condensate piping and related items shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. Provided water pipe size analysis data is incomplete. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2192030 |
Construction | Original | D | 7/31/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, occupancy types, IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2192007 |
Energy | Original | N | 7/31/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2192001 |
Electronic Plan | Original | / | 7/29/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2190753 |
Enumeration | Original | A | 7/25/2025 | AMY | AMY | | | Enumeration | 2189414 |
Electronic Plan | Original | / | 7/25/2025 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2189401 |
Energy | Original | / | 7/24/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2189087 |
Floodplain | Original | N | 7/24/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6232102001) | | Floodplain | 2189086 |