| Electrical | Original | A | 4/27/2026 | DANIELG | DANIELG | | | Electrical | 2299406 |
| Submittal 5 | Original | / | 4/27/2026 | NICOLASV | NICOLASV | Submittal #5 | | Submittal 5 | 2299225 |
| Monument Zoning | Original | A | 4/16/2026 | TOWNOFMON | TOWNOFMON | | bholtztom | Monument Zoning | 2294225 |
| Electrical | Original | D | 4/7/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2290043 |
| Construction | Original | A | 4/7/2026 | JUSTINL | JUSTINL | Revised site map | | Construction | 2289933 |
| Electronic Plan | Original | / | 4/7/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2289927 |
| Submittal 4 | Original | / | 4/7/2026 | QUINTONW | QUINTONW | Submittal #4 | | Submittal 4 | 2289633 |
| Monument Zoning | Original | A | 2/2/2026 | TOWNOFMON | TOWNOFMON | | bholtztom | Monument Zoning | 2262260 |
| Electrical | Original | D | 1/29/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2261124 |
| Construction | Original | A | 1/29/2026 | JUSTINL | JUSTINL | | | Construction | 2261105 |
| Submittal 3 | Original | / | 1/28/2026 | QUINTONW | QUINTONW | Submittal #3 | | Submittal 3 | 2260950 |
| Electrical | Original | D | 12/4/2025 | BERTHA | BERTHA | Review stopped - provide complete plan set - multiple pages missing
Complete re-review necessary. Verify that all previous plan review comments are addressed. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2243967 |
| Monument Zoning | Original | A | 11/6/2025 | TOWNOFMON | TOWNOFMON | | bholtztom | Monument Zoning | 2233689 |
| Electronic Plan | Original | / | 10/31/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2231709 |
| Construction | Original | D | 10/30/2025 | DOUGC | DOUGC | Missing Design Professional Stamps // Wind Speed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2231101 |
| Electronic Plan | Original | / | 10/30/2025 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2231062 |
| Submittal 2 | Original | / | 10/29/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2230331 |
| Tri-Lakes Fire (CSFD) | Original | N | 10/6/2025 | CSFIRE | CSFIRE | FCS N/A | mark.stanwood@colora | Tri-Lakes Fire (CSFD) | 2220189 |
| Tri-Lakes Hazmat (CSFD) | Original | A | 10/6/2025 | CSFIRE | CSFIRE | DFM-C-SV-25-00012 You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources. If you do not have an ACA account at the time of CSFD review, you will need to reach out to the CSFD DFM staff to link the review to your account. DFM Plan Review Fee: $296.00 ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | mark.stanwood@colora | Tri-Lakes Hazmat (CSFD) | 2220188 |
| Tri-Lakes Fire (CSFD) | Original | / | 10/6/2025 | CSFIRE | CSFIRE | | mark.stanwood@colora | Tri-Lakes Fire (CSFD) | 2220131 |
| Monument Zoning | Original | A | 10/1/2025 | TOWNOFMON | TOWNOFMON | | bholtztom | Monument Zoning | 2218216 |
| Electrical | Original | D | 9/30/2025 | BERTHA | BERTHA | Remove PV meter.
Comply with 450.3(B) NEC
Comply with 690.9(D) NEC
Comply with 705.30(F) NEC
Comply with 240.21(C)(6) NEC
Comply with 690.43
Complete re-review of one-line is required. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2217908 |
| Tri-Lakes Hazmat (CSFD) | Original | N | 9/29/2025 | CSFIRE | CSFIRE | | phil.valdez | Tri-Lakes Hazmat (CSFD) | 2216811 |
| Tri-Lakes Fire (CSFD) | Original | N | 9/25/2025 | CSFIRE | CSFIRE | NO FIRE INSPECTION | michael.davis1@color | Tri-Lakes Fire (CSFD) | 2215996 |
| Electronic Plan | Original | / | 9/25/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2215782 |
| Electronic Plan | Original | / | 9/24/2025 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2215650 |
| Enumeration | Original | N | 9/24/2025 | BECKYA | BECKYA | | | Enumeration | 2215571 |
| Electronic Plan | Original | / | 9/24/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2215561 |
| Electronic Plan | Original | / | 9/24/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2215523 |
| Construction | Original | D | 9/24/2025 | JUSTINL | JUSTINL | Missing roof connection documents indicating size and type of rail system, fastening and spacing. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2215508 |
| Electronic Plan | Original | / | 9/24/2025 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2215505 |
| Energy | Original | N | 9/24/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2215501 |
| Floodplain | Original | N | 9/24/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7115101043) | | Floodplain | 2215500 |