| Energy | Original | D | 1/15/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2256864 |
| Electrical | Original | D | 1/15/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2256863 |
| Mechanical | Original | D | 1/12/2026 | TREVORH | TREVORH | Disapproved; How complying with Section 1109.2.5 of the 2021 IMC this code.will need to see The Refrigeration routing on plans.Need to see all condensate drain lines on plans size,material and point of disposal.Need to see elevator Review comments addressed. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2255497 |
| Plumbing | Original | D | 1/12/2026 | SHANEN | SHANEN | CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Elevator sump discharge shall comply with section 301.6 exception. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2255176 |
| Elevators | Original | D | 1/9/2026 | ROBERTV | ROBERTV | See sheets: E201, M104, M105.
RBD Note: Preliminary Shops provided for (2) Otis GEN3 Core Traction Machine Room-Less Elevators, no Generator. A17.1 - 2019, 2023 RBC . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2255001 |
| CO Springs Fire | Original | D | 1/9/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2254956 |
| CO Springs DRE | Original | D | 1/7/2026 | SSADLER | SSADLER | Upload the approved modified development plan and the approval letter. Citywide Impact fees must be paid prior to building permit issuance Assurances for all private improvements must be posted.
Original dp, final recorded plat, final landscaping and irrigation plans are on file and stamped. | | CO Springs DRE | 2254142 |
| City Engr | Original | D | 1/6/2026 | HVO | HVO | Please see previous comment- include a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan, and a copy of the approved Stormwater Enterprise approved Permanent Control Measures in the electronic building permit set | | City Engr | 2253631 |
| EPC Health Dept | Original | D | 1/5/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | EPC Health Dept | 2253279 |
| CSU Water | Original | D | 1/5/2026 | CSUREVIEW | CSUREVIEW | Previous comments partially addressed (detail B4-8 provided). Refer to 2023 Colorado Springs Utilities WaterLESS details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. PSD | PDosch | CSU Water | 2253224 |
| CSU Waste Water | Original | D | 1/5/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. PSD | PDosch | CSU Waste Water | 2253221 |
| Zoning/Planning | Original | / | 1/5/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2253208 |
| CSU Contract Admin. | Original | D | 1/5/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2253175 |
| Construction | Original | D | 1/5/2026 | BPHILLIPS | BPHILLIPS | Provide complete life safety plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2253135 |
| Electronic Plan | Original | / | 12/31/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2252468 |
| Enumeration | Original | A | 12/29/2025 | BECKYA | BECKYA | | | Enumeration | 2251638 |
| Submittal 2 | Original | / | 12/29/2025 | QUINTONW | QUINTONW | Submittal #2 | | Submittal 2 | 2251626 |
| Energy | Original | D | 12/10/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2245908 |
| Plumbing | Original | D | 12/10/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Enumeration comments must be addressed. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, interceptor locations, etc. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Elevator sump discharge does not comply with section 301.6 Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the shaft, provided that they are indirectly connected to the plumbing system. Discharge elevator sump indirectly to a waste receptor capable of handling a minimum of 50 gpm (100 dfu). Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All backgrounds must match per PPRBD plan review requirements. Restroom configuration does not match sheet A103. Provide gpm and/or square footage served by each component of the roof drainage system. See sheets A120 and A122 for all other roof drainage requirements. Hub drain (HD-1) locations shall comply with section 802.4. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2245907 |
| Mechanical | Original | D | 11/25/2025 | TREVORH | TREVORH | Disapproved; Need to see Elevator and construction review comments addressed so mechanical review can move forward * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2241228 |
| Electrical | Original | D | 11/24/2025 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2240623 |
| Electronic Plan | Original | / | 11/24/2025 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2240594 |
| Elevators | Original | D | 11/24/2025 | ROBERTV | ROBERTV | Need site specific shop drawings and power data for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
Also see sheets: A001, A341, M101, E201, P101, P401 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2240535 |
| CO Springs Fire | Original | D | 11/24/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2240507 |
| CO Springs Hazmat | Original | N | 11/24/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2240506 |
| City Engr | Original | D | 11/21/2025 | JDAGNILLO | JDAGNILLO | Include a copy of both the Stormwater Enterprise approved Grading & Erosion Control Plan and Permanent Control Measure (Permanent Water Quality Facility) Plan in the electronic building permit set. | | City Engr | 2239652 |
| EPC Health Dept | Original | D | 11/20/2025 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2239200 |
| CO Springs DRE | Original | D | 11/20/2025 | SSADLER | SSADLER | Once the modification is approved, upload the stamped plans and the approval letter. Upload the final recorded plat. Upload the final approved landscaping and irrigation plans. Citywide impact fees must be paid. Private assurances must be posted. | | CO Springs DRE | 2239135 |
| CSU Contract Admin. | Original | D | 11/17/2025 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2237809 |
| CSU Waste Water | Original | D | 11/17/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | CSU Waste Water | 2237591 |
| CSU Water | Original | D | 11/17/2025 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. Refer to 2023 Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. | PDosch | CSU Water | 2237592 |
| Gas/Elec. Utils | Original | A | 11/17/2025 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. PSD | PDosch | Gas/Elec. Utils | 2237590 |
| Zoning/Planning | Original | / | 11/17/2025 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2237498 |
| Construction | Original | D | 11/17/2025 | BPHILLIPS | BPHILLIPS | Life safety plan, accessibility clearances * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2237469 |
| Electronic Plan | Original | / | 11/12/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2235494 |
| Enumeration | Original | D | 11/10/2025 | BECKYA | BECKYA | It appears main access and front door/office location for this new storage facility is from Powerwood View. The platted address for this side of the lot is 6292 Powerwood View. Please update all plan pages to show the address. In addition, please add tax schedule number and legal description to the Code Study Form. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2235030 |
| Electronic Plan | Original | / | 11/10/2025 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2235005 |
| | Original | / | 11/10/2025 | SYSTEM | SYSTEM | Plan Review fees paid 11/10/2025 for plan submitted 11/03/2025. Submit Date updated to now. Plan now open for review. | | | 2234974 |
| Energy | Original | / | 11/3/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2232058 |
| Floodplain | Original | N | 11/3/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307003025) | | Floodplain | 2232057 |