| CO Springs Fire | Original | D | 11/24/2025 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2240743 |
| CO Springs Hazmat | Original | D | 11/24/2025 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2240742 |
| EPC Health Dept | Original | N | 11/21/2025 | HEALTHDEPT | HEALTHDEPT | Not applicable. MT | mtemple | EPC Health Dept | 2240077 |
| Mechanical | Original | D | 11/19/2025 | DALEH | DALEH | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2238645 |
| Electrical | Original | D | 11/19/2025 | BERTHA | BERTHA | Provide complete one-line with conductor size, type and quantity from utility transformer through all service gear affected by the scope of work - missing Panel L1Z
Provide panel schedules for all panels affected by the scope of work with VA for all branch circuits and calculated load of panel in amps.
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior), and C405.2.8 (Parking Garages), where applicable.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2238602 |
| Electronic Plan | Original | / | 11/19/2025 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2238573 |
| Plumbing | Original | D | 11/19/2025 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to California plumbing code and UPC. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data may be calculated from the point of connection. Show piping to each point of connection and sizing of the piping at each point of connection. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2238441 |
| CSU Water | Original | N | 11/18/2025 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2238394 |
| CSU Waste Water | Original | N | 11/18/2025 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2238393 |
| Construction | Original | D | 11/18/2025 | BPHILLIPS | BPHILLIPS | Reconcile demo plan * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2238363 |
| Energy | Original | N | 11/18/2025 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2238210 |
| Electronic Plan | Original | / | 11/18/2025 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2238182 |
| Enumeration | Original | N | 11/13/2025 | BRENT | BRENT | | | Enumeration | 2236269 |
| Electronic Plan | Original | / | 11/13/2025 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2236245 |
| | Original | / | 11/13/2025 | SYSTEM | SYSTEM | Plan Review fees paid 11/13/2025 for plan submitted 11/13/2025. Submit Date updated to now. Plan now open for review. | | | 2236226 |
| Energy | Original | / | 11/13/2025 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2236222 |
| Floodplain | Original | N | 11/13/2025 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6312114016) | | Floodplain | 2236220 |