| Energy | Original | D | 2/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2272303 |
| Electrical | Original | D | 2/26/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2272302 |
| Electronic Plan | Original | / | 2/26/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2271259 |
| Mechanical | Original | D | 2/25/2026 | TREVORH | TREVORH | Disapproved; Need to see Refrigeration calculations forthe walk in cooler/Freezer * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2271125 |
| Plumbing | Original | D | 2/25/2026 | SHANEN | SHANEN | CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, grease interceptor location, etc. 3/4" cold water serving HB-2 must show compliance with section 608.8 Exception. Provide trash corral plan to show location of yard hydrant. All condensate piping related items shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. Provide a two way fitting or two riser clean-out at each junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. All plumbing fixtures in a restaurant, except restroom fixtures, water entry floor drain, ice machine and hub drains for condensate, must discharge to the grease waste. Multi-compartment sink details must show compliance with section 802.1. Water heater detail must show compliance with 2021 IECC section 404.3. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. ST-12 is for residential use only per manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2270898 |
| Elevators | Original | N | 2/24/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2270600 |
| CO Springs DRE | Original | D | 2/24/2026 | SSADLER | SSADLER | Upload the following: final approved and stamped development plan final recorded plat final approved landscaping and irrigation plans
CDI fees must be paid prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2270175 |
| City Engr | Original | D | 2/23/2026 | HVO | HVO | Please include a copy of the approved Developement Plan, and a copy of the approved the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set | | City Engr | 2269757 |
| EPC Health Dept | Original | D | 2/23/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review is in process and not yet approved. If your assigned plan reviewer has questions, they will contact you directly. For questions, contact Environmental Health at 719-578-3199 option 3.
Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. For questions, contact Environmental Health at 719-578-3199 option 3. KB | KBauer | EPC Health Dept | 2269729 |
| CSU Contract Admin. | Original | D | 2/23/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2269639 |
| CSU Water | Original | D | 2/23/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PLEASE THE DETAIL SHEETS TO THE PLUMBING PLAN. Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.MDA | malcuran | CSU Water | 2269469 |
| CSU Waste Water | Original | D | 2/23/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2269468 |
| Gas/Elec. Utils | Original | D | 2/23/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2269466 |
| Zoning/Planning | Original | / | 2/23/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2269384 |
| Construction | Original | D | 2/20/2026 | BRIANB | BRIANB | See code plan / IECC certificate * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2269323 |
| Energy | Original | / | 2/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC Amended) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2269255 |
| Electronic Plan | Original | / | 2/20/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2269015 |
| Enumeration | Original | D | 1/28/2026 | BECKYA | BECKYA | Provide a site plan within the Architectural sheets for Enumerations approval, to include the surrounding area to clarify the location of this proposed building and trash enclosure. Enumerations should not be marking up the DP or Civil sheets. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2261042 |
| Electronic Plan | Original | / | 1/28/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2261036 |
| | Original | / | 1/28/2026 | SYSTEM | SYSTEM | Plan Review fees paid 01/28/2026 for plan submitted 01/28/2026. Submit Date updated to now. Plan now open for review. | | | 2260899 |
| Energy | Original | / | 1/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2260898 |
| Floodplain | Original | N | 1/28/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6311413003) | | Floodplain | 2260897 |