| Finished Bin (Main) | Original | / | 4/21/2026 | | SCANNING | Location = Finished Bin (Main) by SCANNING | | Finished Bin (Main) | 2296924 |
| CSU Contract Admin. | Original | D | 4/21/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2295789 |
| CSU Waste Water | Original | D | 4/21/2026 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2295705 |
| CSU Water | Original | D | 4/21/2026 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Water | 2295703 |
| CSU Utilities | Original | / | 4/21/2026 | | SCANNING | Location = CSU Utilities by SCANNING | | CSU Utilities | 2295673 |
| City Engr | Original | A | 4/21/2026 | HVO | HVO | A Geological Hazard report or waiver is not required. | | City Engr | 2295657 |
| City Engr | Original | / | 4/17/2026 | | CSFIRE | Location = City Engr by CSFIRE | Jacob.Watson | City Engr | 2294906 |
| CO Springs Fire | Original | D | 4/17/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2294905 |
| CO Springs Hazmat | Original | N | 4/17/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2294902 |
| Fire | Original | / | 3/30/2026 | | SSADLER | Location = Fire by SSADLER | | Fire | 2286169 |
| CO Springs DRE | Original | D | 3/30/2026 | SSADLER | SSADLER | It appears that the temporary use permit application is still under review. Once approved provide the approval letter and the stamped and approved plans. | | CO Springs DRE | 2286168 |
| Zoning/Planning | Original | / | 3/27/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2285985 |
| Zoning/Planning | Original | / | 3/27/2026 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 2285979 |
| Plan Coordinator (Main) | Original | / | 3/27/2026 | | TCRIPPEN | Location = Plan Coordinator (Main) by TCRIPPEN | | Plan Coordinator (Main) | 2285955 |
| Mechanical | Original | A | 3/27/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2285952 |
| Plumbing | Original | A | 3/27/2026 | SHANEN | SHANEN | State of CO DOH approved plans. | | Plumbing | 2285920 |
| Mechanical (Main) | Original | / | 3/18/2026 | | SCANNING | Location = Mechanical (Main) by SCANNING | | Mechanical (Main) | 2281514 |
| Plan Coordinator (Main) | Original | / | 3/18/2026 | | BERTHA | Location = Plan Coordinator (Main) by BERTHA | | Plan Coordinator (Main) | 2281512 |
| Electrical | Original | D | 3/18/2026 | BERTHA | BERTHA | Provide one-line to include all conduit/conductor size, type CU or AL and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Provide withstand rating and available fault current for panels and air conditioning equipment located outside of the structure. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2281511 |
| Electrical (Main) | Original | / | 3/17/2026 | | SCANNING | Location = Electrical (Main) by SCANNING | | Electrical (Main) | 2281350 |
| Plan Coordinator (Main) | Original | / | 3/17/2026 | | JUSTINL | Location = Plan Coordinator (Main) by JUSTINL | | Plan Coordinator (Main) | 2281298 |
| Construction | Original | D | 3/17/2026 | JUSTINL | JUSTINL | Provide stamped letter from design professional indicating if structure is designed to withstand required wind speed and thermal requirements or if any modifications are required. (WALK OK) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2281297 |
| Construction (Main) | Original | / | 3/17/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Construction (Main) | 2281125 |
| Construction (Main) | Original | / | 2/26/2026 | | SCANNING | Location = Construction (Main) by SCANNING | | Construction (Main) | 2272418 |
| Plan Coordinator (Main) | Original | / | 2/26/2026 | | BRENT | Location = Plan Coordinator (Main) by BRENT | | Plan Coordinator (Main) | 2272383 |
| Enumeration | Original | A | 2/26/2026 | BRENT | BRENT | | | Enumeration | 2272382 |
| Enumeration (Main) | Original | / | 2/25/2026 | | SCANNING | Location = Enumeration (Main) by SCANNING | | Enumeration (Main) | 2270924 |
| Plan Coordinator (Main) | Original | / | 2/25/2026 | | MELISSAF | Location = Plan Coordinator (Main) by MELISSAF | | Plan Coordinator (Main) | 2270917 |
| Energy | Original | N | 2/25/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2270916 |
| Floodplain | Original | N | 2/25/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7413112038) | | Floodplain | 2270915 |