| Falcon Fire (CSFD) | Original | D | 4/7/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | Falcon Fire (CSFD) | 2290120 |
| Falcon Hazmat (CSFD) | Original | D | 4/7/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | Falcon Hazmat (CSFD) | 2290119 |
| County Zoning | Original | A | 3/31/2026 | DSDDEAN2 | DSDDEAN2 | Planning and Community Development approved the Site Development Plan at fil no PPR256 on 9/8/2025. PCD has no input on the interior finish of the approved structure. | | County Zoning | 2287139 |
| Energy | Original | D | 3/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2283641 |
| Mechanical | Original | D | 3/24/2026 | TCRIPPEN | TCRIPPEN | Disapproved pending occupant load, * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2283640 |
| Zoning/Planning | Original | / | 3/23/2026 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2283168 |
| Electrical | Original | D | 3/23/2026 | CONNERM | CONNERM | Show compliance with IECC C405.11
Show compliance NEC 517.61 (C) (2)
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2283143 |
| Electronic Plan | Original | / | 3/23/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2283086 |
| EPC Health Dept | Original | N | 3/20/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable. Interior finish of non-regulated facility. AB | abrannon | EPC Health Dept | 2282853 |
| Plumbing | Original | D | 3/20/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. See clouded sections on additional requirements for 2021 IECC block. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Bottle filler does not comply with section 410.3. ST-12 is for residential use only per manufacturer. SD-2MN does not comply with table 608.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2282485 |
| Elevators | Original | N | 3/19/2026 | ANDREAL | ANDREAL | No conveyance in this scope of work. | | Elevators | 2282468 |
| Gas/Elec. Utils | Original | D | 3/19/2026 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities' electric service territory. SSH | SHillman | Gas/Elec. Utils | 2282427 |
| Construction | Original | D | 3/19/2026 | JUSTINL | JUSTINL | See life safety plan, architectural and code study form for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2282356 |
| Energy | Original | / | 3/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2282124 |
| Electronic Plan | Original | / | 3/17/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2281247 |
| Enumeration | Original | A | 2/27/2026 | BRENT | BRENT | | | Enumeration | 2274010 |
| Electronic Plan | Original | / | 2/27/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2273997 |
| | Original | / | 2/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 02/26/2026 for plan submitted 02/26/2026. Submit Date updated to now. Plan now open for review. | | | 2273845 |
| Waste Water Div | Original | / | 2/26/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2273511 |
| Water Division | Original | / | 2/26/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2273510 |
| Energy | Original | / | 2/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2273509 |
| Floodplain | Original | N | 2/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5301104005) | | Floodplain | 2273508 |