| CO Springs DRE | Original | A | 4/10/2026 | SSADLER | SSADLER | Previous approval comments still apply | | CO Springs DRE | 2291744 |
| Energy | Original | D | 4/9/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2290851 |
| Plumbing | Original | D | 4/9/2026 | SHANEN | SHANEN | ST-5 is for residential use only per manufacturer. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2290850 |
| Zoning/Planning | Original | / | 4/8/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2290752 |
| Mechanical | Original | A | 4/8/2026 | TREVORH | TREVORH | Approved; | | Mechanical | 2290719 |
| Electrical | Original | D | 4/8/2026 | CONNERM | CONNERM | Comply with 250.122 (G) * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2290709 |
| Electronic Plan | Original | / | 4/8/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2290699 |
| Construction | Original | A | 4/8/2026 | BPHILLIPS | BPHILLIPS | | | Construction | 2290678 |
| Enumeration | Original | A | 4/8/2026 | BECKYA | BECKYA | | | Enumeration | 2290577 |
| Submittal 2 | Original | / | 4/8/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2290258 |
| CO Springs Fire | Original | A | 4/7/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2290023 |
| CO Springs Hazmat | Original | N | 4/7/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2290022 |
| Energy | Original | D | 3/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2283987 |
| Mechanical | Original | D | 3/24/2026 | TREVORH | TREVORH | Disapproved; Indicate on plans how Rooftop Equipment will be accessed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2283986 |
| City Engr | Original | N | 3/20/2026 | HVO | HVO | | | City Engr | 2282859 |
| EPC Health Dept | Original | N | 3/20/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable. Offices and breakroom remodel only. AB | abrannon | EPC Health Dept | 2282857 |
| Plumbing | Original | D | 3/20/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. ST-8 is for residential use only per manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2282718 |
| CO Springs DRE | Original | A | 3/20/2026 | SSADLER | SSADLER | Approved for commercial interior finish. Use is compatible with the approved development plan. No exterior changes | | CO Springs DRE | 2282678 |
| Electrical | Original | D | 3/20/2026 | CONNERM | CONNERM | Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Comply with 250.122
Provide fault current info for new RTUs * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2282568 |
| Electronic Plan | Original | / | 3/20/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2282530 |
| Elevators | Original | N | 3/20/2026 | ANDREAL | ANDREAL | No conveyance in this scope of work. | | Elevators | 2282513 |
| CSU Contract Admin. | Original | N | 3/19/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved and applicable development fees/charges paid - master meter configuration. AMS | ASweet | CSU Contract Admin. | 2282430 |
| Zoning/Planning | Original | / | 3/19/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2282278 |
| CSU Water | Original | N | 3/19/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2282161 |
| CSU Waste Water | Original | N | 3/19/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2282158 |
| Gas/Elec. Utils | Original | A | 3/19/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | Gas/Elec. Utils | 2282154 |
| Construction | Original | D | 3/19/2026 | BPHILLIPS | BPHILLIPS | Restroom access * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2282142 |
| Electronic Plan | Original | / | 3/18/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2281507 |
| Enumeration | Original | A | 3/17/2026 | BECKYA | BECKYA | | | Enumeration | 2281411 |
| Electronic Plan | Original | / | 3/17/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2281408 |
| | Original | / | 3/17/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/17/2026 for plan submitted 02/27/2026. Submit Date updated to now. Plan now open for review. | | | 2281103 |
| Energy | Original | / | 2/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC (2021 IECC) is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2273972 |
| Floodplain | Original | N | 2/27/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5505001003) | | Floodplain | 2273971 |