| Energy | Original | D | 3/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2282452 |
| Electrical | Original | D | 3/19/2026 | BERTHA | BERTHA | Provide UPS detail - clarify compliance with 250.122
Verify compliance with 250.102(C)(1) . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2282451 |
| Mechanical | Original | D | 3/19/2026 | TREVORH | TREVORH | Disapproved; Missing Duct sizing throughout plan.provide point of connection symbol where applicable * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2282355 |
| CO Springs DRE | Original | A | 3/19/2026 | SSADLER | SSADLER | Approved for commercial interior finish. Use is compatible with the approved development plan. No changes to the exterior, parking, or occupancy | | CO Springs DRE | 2282183 |
| CO Springs Fire | Original | D | 3/19/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2282106 |
| CO Springs Hazmat | Original | D | 3/19/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2282105 |
| Electronic Plan | Original | / | 3/19/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2282042 |
| Plumbing | Original | D | 3/19/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to California plumbing code. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2282003 |
| Elevators | Original | N | 3/19/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2281964 |
| CSU Contract Admin. | Original | N | 3/19/2026 | CSUAPPSPRM | CSUAPPSPRM | No applicable fees required for this plan set.
AMS | ASweet | CSU Contract Admin. | 2281916 |
| CSU Water | Original | D | 3/18/2026 | CSUREVIEW | CSUREVIEW | Submit a Commercial Water Meter Sizing Form (CWMSF) to verify water service, meter size, and payment of development charges/fees. Form can be found at: https://www.csu.org/hubfs/Document-Library/CommercialWaterMeterSizing.pdf?csf=1&e=IzaoDL
PSD ***Form must be submitted to cca@csu.org. Contact Customer Contract Administration at 719-668-8111 with any questions.*** | PDosch | CSU Water | 2281846 |
| CSU Waste Water | Original | N | 3/18/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2281845 |
| Gas/Elec. Utils | Original | A | 3/18/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. PSD | PDosch | Gas/Elec. Utils | 2281843 |
| Zoning/Planning | Original | / | 3/18/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2281836 |
| Construction | Original | A | 3/18/2026 | DOUGC | DOUGC | | | Construction | 2281794 |
| Electronic Plan | Original | / | 3/18/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2281735 |
| Enumeration | Original | A | 3/18/2026 | BRENT | BRENT | | | Enumeration | 2281608 |
| Electronic Plan | Original | / | 3/18/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2281590 |
| | Original | / | 3/17/2026 | SYSTEM | SYSTEM | Plan Review fees paid 03/17/2026 for plan submitted 03/17/2026. Submit Date updated to now. Plan now open for review. | | | 2281268 |
| Energy | Original | / | 3/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2280990 |
| Floodplain | Original | N | 3/17/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5505001001) | | Floodplain | 2280989 |