| CO Springs DRE | Original | A | 4/29/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No exterior changes approved with this permit. | | CO Springs DRE | 2300747 |
| CO Springs Fire | Original | D | 4/29/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2300595 |
| CO Springs Hazmat | Original | D | 4/29/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2300594 |
| Energy | Original | D | 4/29/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2300475 |
| Electrical | Original | D | 4/29/2026 | BERTHA | BERTHA | Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10 of the 2021 IECC.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2300474 |
| Mechanical | Original | D | 4/29/2026 | TREVORH | TREVORH | Disapproved; Need to provide gas pipe to RTU connection detail * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2300391 |
| CSU Waste Water | Original | N | 4/28/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2300215 |
| CSU Water | Original | N | 4/28/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2300214 |
| Zoning/Planning | Original | / | 4/28/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2300014 |
| Plumbing | Original | N | 4/28/2026 | SHANEN | SHANEN | No plumbing scope indicated. | | Plumbing | 2299991 |
| Electronic Plan | Original | / | 4/28/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2299987 |
| Energy | Original | / | 4/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2299944 |
| Construction | Original | D | 4/28/2026 | DOUGC | DOUGC | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2299943 |
| Electronic Plan | Original | / | 4/23/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2298341 |
| Electronic Plan | Original | / | 4/23/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2298170 |
| Enumeration | Original | N | 4/17/2026 | AMY | AMY | | | Enumeration | 2294593 |
| Electronic Plan | Original | / | 4/17/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2294574 |
| | Original | / | 4/17/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/17/2026 for plan submitted 04/13/2026. Submit Date updated to now. Plan now open for review. | | | 2294567 |
| Energy | Original | / | 4/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2292122 |
| Floodplain | Original | N | 4/13/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233304002) | | Floodplain | 2292121 |