| Energy | Original | D | 6/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2326427 |
| Electrical | Original | D | 6/24/2026 | CONNERM | CONNERM | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2326426 |
| Energy | Original | / | 6/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2326424 |
| Energy | Original | A | 6/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2325905 |
| Electrical | Original | A | 6/24/2026 | CONNERM | CONNERM | | | Electrical | 2325904 |
| Submittal 2 | Original | / | 6/23/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2325744 |
| CO Springs Fire | Original | A | 6/1/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2314965 |
| CO Springs Hazmat | Original | N | 6/1/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2314964 |
| Energy | Original | D | 5/21/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2310423 |
| Mechanical | Original | A | 5/21/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2310422 |
| CO Springs DRE | Original | A | 5/18/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No exterior changes approved with this permit. | | CO Springs DRE | 2308461 |
| Electrical | Original | D | 5/14/2026 | CONNERM | CONNERM | The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10
Provide full site plan with locations of all panels under scope of work. This only shows panel R1A
Fault current information (SCCR, AIC, SCA) at all new panelboards and switchboards
Provide conductor size type and quantity * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2307190 |
| Electronic Plan | Original | / | 5/14/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2307083 |
| Zoning/Planning | Original | / | 5/13/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2307074 |
| CSU Water | Original | N | 5/13/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | CSU Water | 2307017 |
| CSU Waste Water | Original | N | 5/13/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 2307015 |
| Plumbing | Original | A | 5/13/2026 | SHANEN | SHANEN | | | Plumbing | 2306892 |
| Construction | Original | A | 5/13/2026 | BRIANB | BRIANB | | | Construction | 2306870 |
| Electronic Plan | Original | / | 5/11/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2305832 |
| Enumeration | Original | N | 4/21/2026 | BECKYA | BECKYA | | | Enumeration | 2296974 |
| Floodplain | Original | N | 4/21/2026 | BECKYA | BECKYA | | | Floodplain | 2296969 |
| Electronic Plan | Original | / | 4/21/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2296968 |
| | Original | / | 4/21/2026 | SYSTEM | SYSTEM | Plan Review fees paid 04/21/2026 for plan submitted 04/21/2026. Submit Date updated to now. Plan now open for review. | | | 2295707 |
| Energy | Original | / | 4/21/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2295667 |
| Floodplain | Original | / | 4/21/2026 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6305202014) | | Floodplain | 2295666 |