| Energy | Original | D | 5/14/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2307655 |
| Mechanical | Original | D | 5/14/2026 | TREVORH | TREVORH | Disapproved; Ensure Colorado spring utilities required distances have been met * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2307654 |
| County Zoning | Original | A | 5/14/2026 | DSDLANCTO | DSDLANCTO | Road Impact Fee Calculation Notes: What I am seeing on the approved site plan is a 10ksf building and areas marked for outdoor storage. I measured the outdoor storage area to be about 2325sf. I did the RIF based on the Mini warehouse/ outdoor storage land use for all of the square footage. Mini warehouse: $447/ksf x 12.325ksf = $5,509 | | County Zoning | 2307236 |
| Zoning/Planning | Original | / | 5/14/2026 | DSDLANCTO | DSDLANCTO | In Current Review by DSDLANCTO | | Zoning/Planning | 2307195 |
| CSU Contract Admin. | Original | D | 5/13/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2307050 |
| Gas/Elec. Utils | Original | A | 5/13/2026 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. MLW | mlwilliams | Gas/Elec. Utils | 2307038 |
| Electrical | Original | D | 5/13/2026 | CONNERM | CONNERM | Fault current information (SCCR, AIC, SCA) at all new air conditioning refrigeration equipment.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Remove ground from service conductors * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2306779 |
| Plumbing | Original | D | 5/13/2026 | SHANEN | SHANEN | Security water/waste water dept. approved construction drawings and utility service plan required to verify the plumbing plans correspond with the Security water/waste water dept. approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2306777 |
| Electronic Plan | Original | / | 5/13/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2306748 |
| Construction | Original | D | 5/13/2026 | SHELLEY | SHELLEY | See site plan, sections, IECC, structural * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2306731 |
| Electronic Plan | Original | / | 5/13/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2306655 |
| Enumeration | Original | D | 5/12/2026 | BRENT | BRENT | Each tenant space in this building will need to be assigned a suite number which follows the PPRBD secondary addressing guidelines available on our website. These secondary addresses need to be shown on every page where the multi-tenant layout is shown. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2305951 |
| Electronic Plan | Original | / | 5/11/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2305909 |
| | Original | / | 5/11/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/11/2026 for plan submitted 05/01/2026. Submit Date updated to now. Plan now open for review. | | | 2305904 |
| Hazmat | Original | / | 5/1/2026 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2301661 |
| Fire | Original | / | 5/1/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2301662 |
| Waste Water Div | Original | / | 5/1/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2301663 |
| Water Division | Original | / | 5/1/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2301660 |
| Energy | Original | / | 5/1/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2301659 |
| Floodplain | Original | N | 5/1/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6502002012) | | Floodplain | 2301658 |