| | Original | / | 9/28/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2364464 |
| Submittal 4 | Original | / | 9/28/2026 | MELISSAF | MELISSAF | Submittal #4 | | Submittal 4 | 2364463 |
| Ellicott Hazmat | Original | A | 9/25/2026 | ELLICOTTFIRE | ELLICOTTFIRE | Final inspection and hazmat permit required. | ELLICOTTFD | Ellicott Hazmat | 2363874 |
| Ellicott Fire | Original | A | 9/25/2026 | ELLICOTTFIRE | ELLICOTTFIRE | Final Fire Inspection Required. | ELLICOTTFD | Ellicott Fire | 2363872 |
| Energy | Original | D | 9/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2361221 |
| Electrical | Original | D | 9/18/2026 | CONNERM | CONNERM | Provide fault current withstand rating (SCCR) for transfer switch * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2361220 |
| Construction | Original | A | 9/18/2026 | SHELLEY | SHELLEY | | | Construction | 2361102 |
| Enumeration | Original | A | 9/18/2026 | BECKYA | BECKYA | | | Enumeration | 2360927 |
| | Original | / | 9/18/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee(s) Paid | | | 2360922 |
| | Original | / | 9/18/2026 | SYSTEM | SYSTEM | Resubmittal Processing Fee Due | | | 2360892 |
| Submittal 3 | Original | / | 9/18/2026 | MELISSAF | MELISSAF | Submittal #3 | | Submittal 3 | 2360891 |
| Ellicott Hazmat | Original | D | 9/1/2026 | ELLICOTTFIRE | ELLICOTTFIRE | See Ellicott Fire entry for hazmat comments | ELLICOTTFD | Ellicott Hazmat | 2355181 |
| Ellicott Fire | Original | D | 9/1/2026 | ELLICOTTFIRE | ELLICOTTFIRE | No Hazmat Inventory Statement per adopted 2021 IFC 5001.5.2 has been provided and is required per code.
Provide the energy stored with indoor batteries per 2021 IFC Table 1207.1.1. | ELLICOTTFD | Ellicott Fire | 2355178 |
| County Zoning | Original | A | 8/28/2026 | DSDUHLER | DSDUHLER | | | County Zoning | 2353930 |
| Zoning/Planning | Original | / | 8/28/2026 | DSDUHLER | DSDUHLER | In Current Review by DSDUHLER | | Zoning/Planning | 2353673 |
| CSU Contract Admin. | Original | D | 8/27/2026 | CSUAPPSPRM | CSUAPPSPRM | Address is not in CSU service territory.
AMS | ASweet | CSU Contract Admin. | 2353492 |
| Energy | Original | D | 8/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2353035 |
| Electrical | Original | D | 8/27/2026 | CONNERM | CONNERM | Provide fault current info (SCA, SCCR, AIC) for all new panels and transfer equipment * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2353034 |
| Electronic Plan | Original | / | 8/27/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2353013 |
| Construction | Original | D | 8/27/2026 | SHELLEY | SHELLEY | Design loads are still not specified on foundation design. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2352997 |
| Enumeration | Original | A | 8/27/2026 | BECKYA | BECKYA | | | Enumeration | 2352890 |
| Submittal 2 | Original | / | 8/27/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2352820 |
| County Zoning | Original | D | 6/1/2026 | DSDLANCTO | DSDLANCTO | Please submit either the stamped site plan from PPR2534 or the modified version that was approved per the email 5/15/26. | | County Zoning | 2314877 |
| Mechanical | Original | A | 5/27/2026 | DALEH | DALEH | Exterior belly tank generator | | Mechanical | 2312568 |
| Energy | Original | D | 5/22/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2311251 |
| Mechanical | Original | D | 5/22/2026 | DALEH | DALEH | will the back up generator be a separate submittal ? or part of this submittal ? * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2311250 |
| Ellicott Fire | Original | D | 5/17/2026 | ELLICOTTFIRE | ELLICOTTFIRE | Water supply not provided in accordance with 2021 IFC Chapter 5 and Appendices B and C. Fire alarm and suppression may be required for batteries and not addressed in submitted documentation. | ELLICOTTFD | Ellicott Fire | 2308378 |
| Ellicott Hazmat | Original | D | 5/17/2026 | ELLICOTTFIRE | ELLICOTTFIRE | Hazardous materials information has not been provided. What is the quantity of and classification of the generator fuel to be uses? What kind of batteries will be used and what are the associated hazards that a hydrogen detector is provided? Do these batteries require explosion venting, a fire alarm system, fire suppression system, a specific CFM of air change? Provide compliance with Appendix H of the 2021 IFC. | ELLICOTTFD | Ellicott Hazmat | 2308377 |
| Zoning/Planning | Original | / | 5/14/2026 | DSDLANCTO | DSDLANCTO | In Current Review by DSDLANCTO | | Zoning/Planning | 2307158 |
| Plumbing | Original | N | 5/14/2026 | SHANEN | SHANEN | U occupancy. No plumbing scope indicated. State of CO DOH approved plans. | | Plumbing | 2307079 |
| CSU Contract Admin. | Original | D | 5/13/2026 | CSUAPPSPRM | CSUAPPSPRM | Address is out of CSU service area. Please work with applicable utility providers.
AMS | ASweet | CSU Contract Admin. | 2307044 |
| Electrical | Original | A | 5/13/2026 | CONNERM | CONNERM | | | Electrical | 2307021 |
| Electronic Plan | Original | / | 5/13/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2307018 |
| Construction | Original | D | 5/13/2026 | SHELLEY | SHELLEY | See foundation design * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2307012 |
| Electronic Plan | Original | / | 5/13/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2307003 |
| Floodplain | Original | N | 5/7/2026 | KEITH | KEITH | | | Floodplain | 2304709 |
| Enumeration | Original | A | 5/7/2026 | BECKYA | BECKYA | | | Enumeration | 2304275 |
| | Original | / | 5/7/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/07/2026 for plan submitted 05/01/2026. Submit Date updated to now. Plan now open for review. | | | 2304238 |
| Water Division | Original | / | 5/1/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2301912 |
| Waste Water Div | Original | / | 5/1/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2301913 |
| Energy | Original | / | 5/1/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2301911 |
| Floodplain | Original | / | 5/1/2026 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 3407000001) | | Floodplain | 2301909 |