| Cherokee Waste Water | Original | D | 6/22/2026 | CHEROKEEMETRO | CHEROKEEMETRO | Show that new wastewater lines route through existing Oil Separator | bzembles | Cherokee Waste Water | 2325084 |
| Cherokee Water | Original | A | 6/22/2026 | CHEROKEEMETRO | CHEROKEEMETRO | | bzembles | Cherokee Water | 2325083 |
| EPC Health Dept | Original | A | 6/18/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review by Kevin Bauer on 03/27/2025. A pre-operational inspection was conducted by EPCPH on 03/27/2025. Per Albert Caroccio, Principal, "no new work was or has been conducted. The plan review process was probably submitted by a previous contractor who they are not working with anymore". AM | Amanda Furno | EPC Health Dept | 2323325 |
| Mechanical | Original | D | 6/16/2026 | TREVORH | TREVORH | Disapproved; Need to provide the Refrigeration calculations for the new mini split system. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2322010 |
| Electrical | Original | D | 6/16/2026 | CONNERM | CONNERM | Lighting controls must be clearly shown and must comply with C405.2
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2321964 |
| Electronic Plan | Original | / | 6/16/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2321940 |
| Plumbing | Original | D | 6/16/2026 | SHANEN | SHANEN | Hand sink discharging through an indirect waste connection does not comply with section 802.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2321679 |
| Construction | Original | D | 6/15/2026 | DOUGC | DOUGC | Rated Assemblies // Wall Tags // CSF * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2321555 |
| Energy | Original | N | 6/15/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2321554 |
| Electronic Plan | Original | / | 6/15/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2321348 |
| Enumeration | Original | N | 5/27/2026 | BRENT | BRENT | | | Enumeration | 2312446 |
| Electronic Plan | Original | / | 5/27/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2312419 |
| | Original | / | 5/27/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/27/2026 for plan submitted 05/26/2026. Submit Date updated to now. Plan now open for review. | | | 2312194 |
| Fire | Original | / | 5/26/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2312171 |
| Hazmat | Original | / | 5/26/2026 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2312170 |
| Energy | Original | / | 5/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2312169 |
| Floodplain | Original | N | 5/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5407409002) | | Floodplain | 2312168 |