| CO Springs Fire | Original | D | 7/10/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2333285 |
| CO Springs Hazmat | Original | N | 7/10/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2333284 |
| Energy | Original | D | 6/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2328866 |
| Mechanical | Original | D | 6/30/2026 | TREVORH | TREVORH | Disapproved; This Mechanical submittal package is missing the gas piping sheets * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2328865 |
| Electrical | Original | D | 6/17/2026 | CONNERM | CONNERM | Clarify OCPD size for this transformer. Panel schedule says 150A. Transformer schedule says 60A. One line has 100A disconnect. Must comply with 450.3
Show all OCPD sizes on one-line
Fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Split receptacles will still need to labeled as controlled
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2322718 |
| Electronic Plan | Original | / | 6/17/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2322585 |
| Plumbing | Original | D | 6/17/2026 | SHANEN | SHANEN | All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. No plumbing scope indicated. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2322469 |
| CO Springs DRE | Original | A | 6/17/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to landscaping, footprint, or parking. No exterior changes approved with this permit. | | CO Springs DRE | 2322381 |
| Electronic Plan | Original | / | 6/17/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2322375 |
| CSU Water | Original | N | 6/16/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | CSU Water | 2322305 |
| CSU Waste Water | Original | N | 6/16/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 2322302 |
| Zoning/Planning | Original | / | 6/16/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2322244 |
| Construction | Original | D | 6/16/2026 | JUSTINL | JUSTINL | See architectural and code study form for review comments.
After further discussions with mechanical reviewer, RTU 5 is new and being added to roof. Provide engineer letter or plan for new RTU 5 weighing in excess of 11,000 lbs to existing structure.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2322230 |
| Electronic Plan | Original | / | 6/16/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2322018 |
| Enumeration | Original | N | 5/29/2026 | BECKYA | BECKYA | | | Enumeration | 2313886 |
| Electronic Plan | Original | / | 5/28/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2313747 |
| | Original | / | 5/28/2026 | SYSTEM | SYSTEM | Plan Review fees paid 05/28/2026 for plan submitted 05/28/2026. Submit Date updated to now. Plan now open for review. | | | 2313731 |
| Energy | Original | / | 5/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2313632 |
| Floodplain | Original | N | 5/28/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6207108005) | | Floodplain | 2313631 |