| CO Springs Fire | Original | D | 7/10/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Fire | 2333245 |
| CO Springs Fire | Original | / | 7/10/2026 | CSFIRE | CSFIRE | | jt09ff | CO Springs Fire | 2333244 |
| CO Springs Fire | Original | D | 7/10/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Fire | 2333242 |
| CO Springs Hazmat | Original | D | 7/10/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Hazmat | 2333239 |
| City Engr | Original | D | 6/24/2026 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set.
Informational comment: Revised street construction plans are currently under review and must be approved so construction on public infrastructure, including adjacent public street and accesses, can begin (see Project Dox #STM-REV26-0288)." | | City Engr | 2326237 |
| CO Springs DRE | Original | D | 6/23/2026 | SSADLER | SSADLER | There are entitlements that are still under review. Once approved, upload the approved stamped plans, the final recorded plat, the final approved landscaping and irrigation plans, and the approval letters. All impact fees are due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov
Due to policy changes, assurances for all private improvements are now due at the time of C/O | | CO Springs DRE | 2325202 |
| EPC Health Dept | Original | D | 6/22/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. MT | mtemple | EPC Health Dept | 2324936 |
| CSU Contract Admin. | Original | D | 6/22/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing form and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111. JMD | jdemello | CSU Contract Admin. | 2324779 |
| CSU Water | Original | D | 6/22/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Water | 2324700 |
| CSU Waste Water | Original | D | 6/22/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Waste Water | 2324699 |
| Energy | Original | D | 6/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2324095 |
| Mechanical | Original | D | 6/19/2026 | TREVORH | TREVORH | Disapproved; Mechanical submittal is Missing the Gas piping plan sheets * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2324094 |
| Plumbing | Original | D | 6/19/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping related items shall be on the mechanical plans. Remove ALL references to gas piping from the plumbing plans. Provide isometric drawings for the DWV and water distribution piping. Water service sizing does not match sheet U1.1. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Water heater detail must show compliance with IECC section C404.3. Provide gpm and/or square footage served by each component of the roof drain system. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2323888 |
| Electrical | Original | D | 6/19/2026 | CONNERM | CONNERM | The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Controlled receptacles must be shown on the plan per C405.11
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2323887 |
| Electronic Plan | Original | / | 6/19/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2323867 |
| Elevators | Original | N | 6/18/2026 | ANDREAL | ANDREAL | No conveyance in this scope of work. | | Elevators | 2323809 |
| Gas/Elec. Utils | Original | D | 6/18/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. PSD | PDosch | Gas/Elec. Utils | 2323751 |
| Zoning/Planning | Original | / | 6/18/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2323749 |
| Construction | Original | D | 6/18/2026 | BRIANB | BRIANB | See architectural site plan / sheets G020 / A101 / A210 / A330 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2323733 |
| Energy | Original | / | 6/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2323683 |
| Electronic Plan | Original | / | 6/16/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2322188 |
| Enumeration | Original | D | 6/5/2026 | BRENT | BRENT | The final plat for Veterans Villa Fil. No. 1 has not been recorded. Enumerations will not approve until we have a copy of the recorded plat in our database. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2317169 |
| Electronic Plan | Original | / | 6/5/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2317084 |
| | Original | / | 6/5/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/05/2026 for plan submitted 05/29/2026. Submit Date updated to now. Plan now open for review. | | | 2317071 |
| Energy | Original | / | 5/29/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2313883 |
| Floodplain | Original | N | 5/29/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5500000453) | | Floodplain | 2313882 |