| Energy | Original | D | 7/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2335184 |
| Plumbing | Original | D | 7/16/2026 | SHANEN | SHANEN | Preliminary review. Provide plumbing plans that comply with PPRBD commercial plumbing plan review requirements. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Remove all references to other plumbing codes and jurisdictions. Provide plumbing floor plans for the entire building showing DWV and water distribution piping throughout.Show DFU and WSFU served by each combined section of the building drain and water distribution systems. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Reference 2021 IPC throughout. 2" SAN serving WMB and DRAIN is not in compliance with section 406.2. Make corrections throughout. Provide roof plan to show sizing for roof drain conductors, downspouts and overflow scuppers. Provide gpm and/or square footage served by components of the roof drain system. All condensate piping related items shall be on the mechanical plans. Remove all references to condensate piping from the plumbing plans. Hub drain located in return air plenum is not in compliance with section 802.4. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2335183 |
| Electrical | Original | D | 7/13/2026 | BERTHA | BERTHA | Pending approval in Enumerations - Multi-meter services must include a list of enumerated addresses on the one-line diagram - Secondary addressing must be approved by Enumerations.
Pending approval in Elevators
Provide elevator feeder size, type, and quantity on the one line.
Provide elevator over current device size ( Ampacity) on the one line.
Provide elevator horsepower on the one line.
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Remove parallel neutral - remove equipment ground from service conductors.
Provide all conductor size, type and quantity.
Comply with 2021 IECC;
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior), and C405.2.8 (Parking Garages), where applicable.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Complete re-review necessary.
. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2333739 |
| CO Springs DRE | Original | D | 7/13/2026 | SSADLER | SSADLER | Upload the following documents: approved and stamped development plans final approved landscaping and irrigation plans final recorded plat
Citywide impact fees are due prior to building permit issuance.
Due to policy changes, assurances for all private improvements are now due at the time of C/O | | CO Springs DRE | 2333348 |
| City Engr | Original | D | 7/9/2026 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set.
Informational comment: Revised street construction plans are currently under review and must be approved so construction on public infrastructure, including adjacent public street and accesses, can begin (see Project Dox #STM-REV26-0288)." | | City Engr | 2332339 |
| EPC Health Dept | Original | D | 7/9/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2332331 |
| Mechanical | Original | D | 7/9/2026 | TREVORH | TREVORH | Disapproved; * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2332271 |
| Elevators | Original | D | 7/8/2026 | ROBERTV | ROBERTV | Need site specific shop drawings, power data and controller short circuit current rating (SCCR) for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
See Sheets: A300, S201, E101, E102, E103, E104, E105, E501, M500, MP102, MP105, P500 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2332027 |
| Gas/Elec. Utils | Original | D | 7/8/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | Gas/Elec. Utils | 2332012 |
| CSU Waste Water | Original | D | 7/8/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 2332011 |
| CSU Water | Original | D | 7/8/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. DMM | dmakings | CSU Water | 2332007 |
| Zoning/Planning | Original | / | 7/8/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2331950 |
| CSU Contract Admin. | Original | D | 7/8/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2331885 |
| Energy | Original | / | 7/8/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2331873 |
| Construction | Original | D | 7/8/2026 | BRIANB | BRIANB | accessibility / mixed occupancies / fire rated assemblies / IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2331872 |
| Electronic Plan | Original | / | 7/7/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2330921 |
| Electronic Plan | Original | / | 6/16/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2322190 |
| Enumeration | Original | D | 6/5/2026 | BRENT | BRENT | The final plat for Veterans Villa Fil. No. 1 has not been recorded. Enumerations will not approve until we have a copy of the recorded plat in our database. The secondary addressing shown has the apartment numbers increasing from the middle point outward. The apartment numbering should start with 101 at one end and continue all the way to the other end. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2317238 |
| Electronic Plan | Original | / | 6/5/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2317210 |
| | Original | / | 6/5/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/05/2026 for plan submitted 05/29/2026. Submit Date updated to now. Plan now open for review. | | | 2317082 |
| Energy | Original | / | 5/29/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2313907 |
| Floodplain | Original | N | 5/29/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5500000453) | | Floodplain | 2313906 |