| CO Springs Fire | Original | D | 7/16/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Fire | 2335361 |
| CO Springs Hazmat | Original | D | 7/16/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Hazmat | 2335359 |
| CO Springs DRE | Original | D | 6/30/2026 | SSADLER | SSADLER | Upload the approved development plan to show that the use is allowed. | | CO Springs DRE | 2329190 |
| Energy | Original | D | 6/29/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2328125 |
| Mechanical | Original | D | 6/29/2026 | TREVORH | TREVORH | Disapproved; Need to turn the ceiling layer off and provide Column lines to match the Architectural pages * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2328124 |
| Electrical | Original | D | 6/25/2026 | CONNERM | CONNERM | Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Controlled receptacles must be shown on the plan per C405.11
Provide fault current information (SCCR, AIC, SCA) at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2327059 |
| Electronic Plan | Original | / | 6/25/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2327053 |
| CSU Water | Original | N | 6/25/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2326871 |
| CSU Waste Water | Original | N | 6/25/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2326870 |
| Plumbing | Original | D | 6/25/2026 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. 3-comp sink must show compliance with section 802.1. All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2326815 |
| Zoning/Planning | Original | / | 6/25/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2326695 |
| Construction | Original | D | 6/25/2026 | JUSTINL | JUSTINL | See code study, architectural and structural plans for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2326680 |
| Energy | Original | / | 6/25/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2326678 |
| Electronic Plan | Original | / | 6/23/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2325276 |
| Enumeration | Original | D | 6/15/2026 | BRENT | BRENT | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2321441 |
| Electronic Plan | Original | / | 6/15/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2321430 |
| | Original | / | 6/15/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/15/2026 for plan submitted 06/10/2026. Submit Date updated to now. Plan now open for review. | | | 2321219 |
| Energy | Original | / | 6/10/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2318901 |
| Floodplain | Original | N | 6/10/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418324045) | | Floodplain | 2318900 |