Plan Details
Clear
Permits
By Address
By Permit Number
Fee Calculator
Plans
By Address
List of Plans
Home
Plan #
  
Type
 
Plan
Owner
Address
6250 GOLDFIELD DR, COLORADO SPRINGS, CO 80911
Parcel Info
5500000164
Truss P/SF
30 (Elevation: 5,821 Feet)
Project
CELL SITE MODIFICATION - VERIZON (
437
)
Type Of Plan
Normal
Review Type
Electronic
Fire District
SECURITY FIRE PROTECTION DISTRICT
Submit Date
Approval Date
Location
Plan Image
View Plan Image
Download Plan Image
Map
Google Map
Yahoo Maps
Bing Maps
MapQuest
GIS Map
County Map & Data
PPRBD Directions
Required Departments: 9
By checking this box, you agree to the following:
Overtime reviews are billed at $100/hour of review time.
Requesting overtime is optional. If I don’t request it, my plan will still be reviewed in the order submitted.
Overtime reviews are dependent on staff availability, so there is no guarantee that the review will be expedited. You will only be charged overtime fees if we are able to perform those reviews. If no one is available to take that review on an overtime basis, your plan may end up being reviewed in the regular sequence.
Required Departments and Log Entries
Department
Status
Approve Overtime
Overtime
Overtime_2
BoundColumn_2
Department
Construction
N
0
C
Construction
Electrical
D
0
E
Electrical
Energy
N
G
Energy
Enumeration
N
0
N
Enumeration
Security Fire
-
0
F
Security Fire
Floodplain
N
0
W
Floodplain
Security Hazmat
-
0
B
Security Hazmat
Mechanical
N
0
M
Mechanical
County Zoning
N
0
Z
County Zoning
Log Entries: 14
Log Details
View Log
Log
Time Summary
Department
Splice
Status
Date
Reviewer
Reviewer
Comment
username
Department
tid
County Zoning
Original
N
7/1/2026
DSDBENSON2
DSDBENSON2
Approved NTWR262. No need for zoning inspection. No road impact fee.
County Zoning
2329834
Mechanical
Original
N
6/30/2026
TREVORH
TREVORH
Not Applicable; for outdoor cell tower cooling fan
Mechanical
2328900
Electrical
Original
D
6/29/2026
CONNERM
CONNERM
Provide series rated combinations
Current limiting is not an acceptable means of mitigating fault current. Provide a series rated or fully rated system.
Identify "Panel A" on site plan
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections.
Plans cannot be re-submitted until all required departments have completed their review. *
Electrical
2328263
Electronic Plan
Original
/
6/29/2026
CONNERM
CONNERM
In Current Review by CONNERM
Electronic Plan
2328168
Zoning/Planning
Original
/
6/29/2026
DSDBENSON2
DSDBENSON2
In Current Review by DSDBENSON2
Zoning/Planning
2328160
Construction
Original
N
6/29/2026
BPHILLIPS
BPHILLIPS
Construction
2328158
Enumeration
Original
N
6/24/2026
BECKYA
BECKYA
If the address for Verizon is 6250 Goldfield Dr, please submit the plan under that address. Enumerations updated the plan and the Code Study form to show the correct address.
Enumeration
2325866
Floodplain
Original
N
6/24/2026
BECKYA
BECKYA
Floodplain
2325864
Electronic Plan
Original
/
6/24/2026
BECKYA
BECKYA
In Current Review by BECKYA
Electronic Plan
2325840
Original
/
6/23/2026
SYSTEM
SYSTEM
Plan Review fees paid 06/23/2026 for plan submitted 06/16/2026. Submit Date updated to now. Plan now open for review.
2325788
Fire
Original
/
6/16/2026
SYSTEM
SYSTEM
You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically.
Fire
2321967
Hazmat
Original
/
6/16/2026
SYSTEM
SYSTEM
You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically.
Hazmat
2321966
Energy
Original
N
6/16/2026
SYSTEM
SYSTEM
Energy Department review not required under 2023 PPRBC when IECC is N/A
Energy
2321965
Floodplain
Original
/
6/16/2026
RBD GIS
RBD GIS
Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 5500000164)
Floodplain
2321963