| Energy | Original | D | 8/17/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2348655 |
| Electrical | Original | D | 8/17/2026 | BERTHA | BERTHA | Comply with previous review comment - Clearly identify all electrical equipment - on the one-line diagram
Comply with previous review comment - Comply with 250.24(A)(1) - on the one-line diagram
Comply with previous review comment - Provide compliance with 250.66 on the one-line diagram - provide conductor size, type and quantity on the one-line diagram.
Comply with previous review comment - Show all overcurrent protection for MCB and feeders on the one-line diagram.
Comply with previous review comment - Provide a note on the one-line indicating “Documentation confirming compliance with 620.62 is required prior to final.”
Pending Elevator review approval.
Comply with previous review comment - Provide the withstand rating for all equipment in the Short Circuit Schedule - add withstand rating to the table.
Provide an overall Electrical EV Site Plan. The EV site plan must clearly indicate the location and type of EV spot. The EV site plan must indicate at minimum the same number of spots as indicated on the Development Plan.
Complete re-review necessary. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2348654 |
| CO Springs DRE | Original | D | 8/13/2026 | SSADLER | SSADLER | Upload the approved stamped development plan. Upload the approval letter. | | CO Springs DRE | 2347303 |
| Mechanical | Original | D | 8/12/2026 | DALEH | DALEH | Waiting on elevator approval Revise mechanical as needed per elevator comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2346983 |
| Electronic Plan | Original | / | 8/12/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2346790 |
| CO Springs Fire | Original | D | 8/12/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2346573 |
| CO Springs Hazmat | Original | D | 8/12/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2346572 |
| Plumbing | Original | D | 8/12/2026 | SHANEN | SHANEN | B occupancy offices require compliance with section 403.1. Remove all references to mechanical systems from the general notes. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, interceptor/separator location, etc. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. All waste piping is 4" per sheet G.P40-01. Elevator sump discharge as described in sheet note 6 does not comply with section 301.6 Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the shaft, provided that they are indirectly connected to the plumbing system. Discharge elevator sump indirectly to a waste receptor capable of handling a minimum of 50 gpm (100 dfu). Show compliance with chapter 11 for the areas not served by RD-1. Show compliance with section 1108 for the roof areas served by RD-1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2346430 |
| City Engr | Original | D | 8/11/2026 | JDAGNILLO | JDAGNILLO | Please address previous comment - Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 2346340 |
| Zoning/Planning | Original | / | 8/11/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2346283 |
| Elevators | Original | D | 8/11/2026 | ROBERTV | ROBERTV | (Elevators #7 and #8)
See sheets: G.A40-00, G.E30-02, G.E60-02, G.M20-00, G.M20-03, G.P20-00
RBD Note: Shop Drawings provided for (2) GEN 3 Edge Otis Machine Room-Less Elevators w/ Controllers in top floor jambs, 3500 lbs / 350 fpm. A17.1 - 2019, 2023 RBC . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2346218 |
| CSU Water | Original | D | 8/11/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Water | 2346143 |
| CSU Waste Water | Original | D | 8/11/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | CSU Waste Water | 2346142 |
| Gas/Elec. Utils | Original | D | 8/11/2026 | CSUREVIEW | CSUREVIEW | See previous comments. Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.MDA | malcuran | Gas/Elec. Utils | 2346140 |
| Construction | Original | A | 8/11/2026 | JUSTINL | JUSTINL | | | Construction | 2345874 |
| Electronic Plan | Original | / | 8/10/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2345637 |
| Enumeration | Original | A | 8/10/2026 | AMY | AMY | | | Enumeration | 2345391 |
| Electronic Plan | Original | / | 8/10/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2345373 |
| Submittal 2 | Original | / | 8/10/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2345309 |
| CSU Contract Admin. | Original | A | 8/4/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development charges and fees paid. MKL | mkluke | CSU Contract Admin. | 2343069 |
| CSU Contract Admin. | Original | / | 8/4/2026 | CSUAPPSPRM | CSUAPPSPRM | | mkluke | CSU Contract Admin. | 2343066 |
| Energy | Original | D | 7/16/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2335097 |
| Mechanical | Original | D | 7/16/2026 | DALEH | DALEH | Waiting on elevator approval Waiting on building plan review comments about rated assemblies See plans for all comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2335096 |
| Electronic Plan | Original | / | 7/15/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2334533 |
| Electrical | Original | D | 7/14/2026 | BERTHA | BERTHA | Provide all conductor size, type and quantity. Beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
Clearly identify all electrical equipment.
Comply with 250.24(A)(1)
Provide compliance with 250.66 on the one-line diagram.
Show all overcurrent protection for MCB and feeders on the one-line diagram.
Provide a note on the one-line indicating “Documentation confirming compliance with 620.62 is required prior to final.”
Provide elevator over current device size ( Ampacity) on the one line.
Pending Elevator review approval.
Provide the withstand rating for all equipment in the Short Circuit Schedule.
Provide all plans.
Complete re-review necessary. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2333995 |
| Plumbing | Original | D | 7/9/2026 | SHANEN | SHANEN | S/B occupancy with an occupant load of 1483 requires compliance with section 403.1. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, sand/oil interceptor location, etc. Provide required CSU variance letter for the indoor sand/oil interceptor. Contact Robert Bowren at 719-668-1735 or fog@csu.org. Elevator sump discharge must show compliance with section 301.6 Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the shaft, provided that they are indirectly connected to the plumbing system. Discharge elevator sump indirectly to a waste receptor capable of handling a minimum of 50 gpm (100 dfu). Show or clarify compliance with section 305.4 Freezing. Show compliance with chapter 11 for the areas not served by RD-1. Show compliance with section 1108 for the roof areas served by RD-1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2332487 |
| Electronic Plan | Original | / | 7/1/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2329284 |
| Elevators | Original | D | 6/30/2026 | ROBERTV | ROBERTV | See sheets: G.A40-00, G.M20-00, G.E20-00. G.E20-01, G.E20-02, G.E20-03, G.E60-02, G.P20.00.
RBD Note: Elevators and Elevator Room HVAC unit connected to Generator Power. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2329272 |
| CO Springs Fire | Original | D | 6/29/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2328469 |
| CO Springs Hazmat | Original | D | 6/29/2026 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2328466 |
| CO Springs DRE | Original | D | 6/29/2026 | SSADLER | SSADLER | Upload the approved stamped development plan. Upload the approval letter. | | CO Springs DRE | 2328066 |
| Gas/Elec. Utils | Original | D | 6/29/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | Gas/Elec. Utils | 2327817 |
| CSU Water | Original | D | 6/29/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Water | 2327812 |
| CSU Waste Water | Original | D | 6/29/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Waste Water | 2327810 |
| City Engr | Original | D | 6/29/2026 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan and a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan in the electronic building permit set. | | City Engr | 2327756 |
| CSU Contract Admin. | Original | D | 6/26/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2327683 |
| Zoning/Planning | Original | / | 6/26/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2327677 |
| Construction | Original | D | 6/26/2026 | JUSTINL | JUSTINL | See code study form, life safety plan, architectural plans for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2327665 |
| Energy | Original | / | 6/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2327421 |
| Enumeration | Original | A | 6/26/2026 | AMY | AMY | Address to Screen wall/fencing added as 4028 Briargate Pkwy | | Enumeration | 2327111 |
| Electronic Plan | Original | / | 6/25/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2326555 |
| Enumeration | Original | A | 6/24/2026 | AMY | AMY | The address on every page of this plan was corrected to 4030 Briiargate Pkwy. Correct the address to the pages that get changed out for other departments. | | Enumeration | 2326401 |
| Electronic Plan | Original | / | 6/24/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2326283 |
| | Original | / | 6/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/24/2026 for plan submitted 06/19/2026. Submit Date updated to now. Plan now open for review. | | | 2326269 |
| Energy | Original | / | 6/19/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2324091 |
| Floodplain | Original | N | 6/19/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6235212001) | | Floodplain | 2324090 |