| CO Springs Hazmat | Original | D | 7/31/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Hazmat | 2341781 |
| CO Springs Fire | Original | D | 7/31/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Fire | 2341780 |
| Electrical | Original | D | 7/23/2026 | BERTHA | BERTHA | Provide feeder tags on the one-line diagram.
Provide all identifying information for electrical equipment on the one-line - voltage, amperage, etc.
Provide overcurrent protection for MCB and feeders on the one line
Provide elevator over current device size ( Ampacity) on the one line
Provide elevator feeder size, type, and quantity on the one line
Provide elevator motor and horsepower on the one line
Pending approval in Elevators - see elevator review comments.
Comply with 240.87
Verify compliance with 230.95
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Comply with 2021 IECC
Recessed lighting must be shown on the lighting schedule and comply with C402.5.10.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Where applicable, Daylight Zones must be shown on the plans per C405.2.4.2 through C405.2.4.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Complete re-review necessary.
. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2338251 |
| Energy | Original | D | 7/23/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2338252 |
| Mechanical | Original | D | 7/22/2026 | DALEH | DALEH | Provide a complete gas piping plan to include all kitchen cooking equipment See plans for complete comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2337390 |
| Electronic Plan | Original | / | 7/21/2026 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 2336923 |
| Plumbing | Original | D | 7/21/2026 | SHANEN | SHANEN | Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans.Provide a piping materials schedule on the plumbing plans. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Show compliance with section 714 if applicable.2"SAN serving WMB and FD does not comply with 406.2. 2"FD does not comply with section 413.4.Clarify how FD-TD serving outdoor showers is in compliance with section 1101.3.3"FD with 3" trap and drain is undersized to serve elevator sump discharge.Shower controls and hand shower location shall comply with ICC A117.1-2017 section 608.4 Controls and hand showers.3/4" CW is undersized to serve two urinals. UR shall be supplied by 3/4" CW per keynote 3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2336834 |
| Electronic Plan | Original | / | 7/21/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2336628 |
| Elevators | Original | D | 7/20/2026 | ROBERTV | ROBERTV | Need site specific shop drawings, power data and controller short circuit current rating (SCCR) for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved
Also See Sheets: A6-01, M2-00, M2-01, E0-04, E2-00, E2-01, E3-00, E3-01, P0-02 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2336620 |
| EPC Health Dept | Original | D | 7/17/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH.
Water recreation plan review required for public or semi-public pool and/or spa. Information may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/public-pools-spa/. Please submit all applications through https://myhealthdepartment.com/EPCPH.
For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2335860 |
| City Engr | Original | D | 7/17/2026 | DSOSA | DSOSA | Please submit financial assurances for the street improvements and drainage,
Also, please include a copy of the Stormwater Enterprise-approved Grading & Erosion Control Plan, and Permanent Control Measures in the electronic building permit set. | | City Engr | 2335600 |
| CO Springs DRE | Original | D | 7/16/2026 | SSADLER | SSADLER | Upload the following documents: final recorded plat final approved landscaping and irrigation plans Citywide impact fees must be paid prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov
Due to policy changes, assurance for private improvements are now due at the time of C/O | | CO Springs DRE | 2335082 |
| CSU Water | Original | D | 7/14/2026 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and/or approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Water | 2334065 |
| CSU Waste Water | Original | D | 7/14/2026 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and/or approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | CSU Waste Water | 2334064 |
| Gas/Elec. Utils | Original | D | 7/14/2026 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and/or approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.MDA | malcuran | Gas/Elec. Utils | 2334063 |
| Zoning/Planning | Original | / | 7/14/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2333967 |
| CSU Contract Admin. | Original | D | 7/14/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 to discuss charges/fees and request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
BS | bschifferstein | CSU Contract Admin. | 2333966 |
| Construction | Original | D | 7/14/2026 | JUSTINL | JUSTINL | See code study form, architectural sheets, IECC document and interior design sheets for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2333952 |
| Electronic Plan | Original | / | 7/14/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2333855 |
| Electronic Plan | Original | / | 7/13/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2333733 |
| Electronic Plan | Original | / | 7/7/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2331482 |
| Enumeration | Original | D | 6/26/2026 | BRENT | BRENT | Final plat for Lakeside Heights at Wolf Ranch Fil. No. 1 has not been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2327388 |
| Floodplain | Original | N | 6/26/2026 | BRENT | BRENT | | | Floodplain | 2327387 |
| Electronic Plan | Original | / | 6/26/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2327386 |
| | Original | / | 6/26/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/26/2026 for plan submitted 06/23/2026. Submit Date updated to now. Plan now open for review. | | | 2327274 |
| Energy | Original | / | 6/23/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2325245 |