| CO Springs Fire | Original | D | 8/5/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2343621 |
| CO Springs Hazmat | Original | D | 8/5/2026 | CSFIRE | CSFIRE | See Fire Comments | Jacob.Watson | CO Springs Hazmat | 2343620 |
| Energy | Original | D | 7/23/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2338003 |
| Plumbing | Original | D | 7/23/2026 | SHANEN | SHANEN | Preliminary review. All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, grease interceptor location, etc. Water service sizing does not match sheet PU1.0. Water service sizing does not match sheet PSP1.1. Clarify keynote 5 detail and page number. Keynote 7 does not match floor plan. Clarify P references throughout plan set (for example P over 2, P over 3, etc.). Clarify compliance with chapter 11 as the architectural plans indicate an internal gutter system. Show compliance with section 1108. Reference 2021 IPC. All floor drains in walk-in coolers and freezers must show compliance with section 802.1.2 Exception. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2338002 |
| Mechanical | Original | D | 7/20/2026 | TREVORH | TREVORH | Disapproved; Need to include on plans, sequence of operation for the interlocks between Make up air, exhaust and ansul valve activation . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2336236 |
| Electronic Plan | Original | / | 7/20/2026 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 2336000 |
| CO Springs DRE | Original | D | 7/17/2026 | SSADLER | SSADLER | Upload the final recorded plat. Citywide impact fees must be paid prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov
Due to policy changes, assurances for private improvements are now due at the time of C/O | | CO Springs DRE | 2335467 |
| Electrical | Original | D | 7/16/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2335378 |
| Electronic Plan | Original | / | 7/16/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2335343 |
| Elevators | Original | N | 7/16/2026 | ANDREAL | ANDREAL | No conveyance in this scope of work. | | Elevators | 2335277 |
| Gas/Elec. Utils | Original | A | 7/15/2026 | CSUREVIEW | CSUREVIEW | Approved development plan provided with permit set. SSH | SHillman | Gas/Elec. Utils | 2334773 |
| CSU Water | Original | D | 7/15/2026 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set.
Additionally, please double check the pipe sizes called out in the key notes on Plumbing Sheet PSP1.1. They do not currently match the utility construction drawings.
Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Water | 2334772 |
| CSU Waste Water | Original | D | 7/15/2026 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set.
Additionally, please double check the pipe sizes called out in the key notes on Plumbing Sheet PSP1.1. They do not currently match the utility construction drawings.
Contact Utilities Development Services at 719-668-8259 with any questions. SSH | SHillman | CSU Waste Water | 2334769 |
| City Engr | Original | D | 7/15/2026 | DSOSA | DSOSA | Please upload the Stormwater Enterprise-approved Grading & Erosion Control Plan.
Also, include the following statement on the architectural/structural plans:
“The private retaining wall system shall be designed by a Colorado registered professional engineer and the responsibility of the construction and maintenance lies with the developer and property owner. The City of Colorado Springs has not reviewed or approved the design, and the Owner(s) hereby releases and forever discharges, and agrees to indemnify, defend and hold harmless, the City of Colorado Springs, its officers, employees, administrators, representatives, agents, successors and assigns, from any and all damages, injuries or accidents which might arise from the retaining wall system or the Project after issuance of a Building Permit” | | City Engr | 2334542 |
| EPC Health Dept | Original | D | 7/15/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH.
Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please submit all applications through https://myhealthdepartment.com/EPCPH.
For questions, contact Environmental Health at 719-578-3199 option 3. AM | Amanda Furno | EPC Health Dept | 2334471 |
| CSU Contract Admin. | Original | D | 7/15/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2334425 |
| Zoning/Planning | Original | / | 7/15/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2334401 |
| Construction | Original | D | 7/15/2026 | BRIANB | BRIANB | See LS1.1 / code study form / fire ratings / structural design / IECC * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2334369 |
| Electronic Plan | Original | / | 7/10/2026 | BRIANB | BRIANB | In Current Review by BRIANB | | Electronic Plan | 2333212 |
| Enumeration | Original | A | 7/6/2026 | BRENT | BRENT | | | Enumeration | 2330716 |
| Electronic Plan | Original | / | 7/6/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2330711 |
| | Original | / | 7/6/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/06/2026 for plan submitted 06/26/2026. Submit Date updated to now. Plan now open for review. | | | 2330706 |
| Energy | Original | / | 6/26/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2327577 |
| Floodplain | Original | N | 6/26/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6220402004) | | Floodplain | 2327575 |