| Falcon Fire (CSFD) | Original | A | 8/17/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | Falcon Fire (CSFD) | 2348515 |
| Falcon Hazmat (CSFD) | Original | N | 8/17/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | Falcon Hazmat (CSFD) | 2348513 |
| Energy | Original | D | 8/13/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2347064 |
| Mechanical | Original | A | 8/13/2026 | DALEH | DALEH | Approved as noted for outside air damper | | Mechanical | 2347063 |
| Electrical | Original | D | 8/11/2026 | DANIELG | DANIELG | Comply with 250.66 NEC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2346069 |
| Plumbing | Original | A | 8/10/2026 | SHANEN | SHANEN | | | Plumbing | 2345568 |
| Construction | Original | D | 8/10/2026 | DOUGC | DOUGC | Rated walls at understair storage area * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2345289 |
| Enumeration | Original | A | 8/10/2026 | BECKYA | BECKYA | | | Enumeration | 2345188 |
| Meridian Ranch Water | Original | A | 8/10/2026 | MERIDIANRANCH | MERIDIANRANCH | | LawrenceGrahem | Meridian Ranch Water | 2345173 |
| Meridian Ranch Waste Water | Original | A | 8/10/2026 | MERIDIANRANCH | MERIDIANRANCH | | LawrenceGrahem | Meridian Ranch Waste Water | 2345172 |
| Submittal 2 | Original | / | 8/7/2026 | NICOLASV | NICOLASV | Submittal #2 | | Submittal 2 | 2345067 |
| Falcon Fire (CSFD) | Original | D | 8/6/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | Falcon Fire (CSFD) | 2344563 |
| Falcon Hazmat (CSFD) | Original | D | 8/6/2026 | CSFIRE | CSFIRE | | chiptaylor | Falcon Hazmat (CSFD) | 2344562 |
| Meridian Ranch Water | Original | D | 7/27/2026 | MERIDIANRANCH | MERIDIANRANCH | Address plumbing comments | LawrenceGrahem | Meridian Ranch Water | 2339594 |
| Meridian Ranch Waste Water | Original | D | 7/27/2026 | MERIDIANRANCH | MERIDIANRANCH | Address plumbing comments | LawrenceGrahem | Meridian Ranch Waste Water | 2339591 |
| Energy | Original | D | 7/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2338686 |
| Plumbing | Original | D | 7/24/2026 | SHANEN | SHANEN | Construction review comments regarding occupancy/occupant loads must be addressed to verify compliance with section 403.1. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. 3/4"DCW is undersized to serve downstream fixtures. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2338685 |
| County Zoning | Original | A | 7/22/2026 | DSDUHLER | DSDUHLER | | | County Zoning | 2337400 |
| Electrical | Original | D | 7/21/2026 | DANIELG | DANIELG | * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2336783 |
| Mechanical | Original | D | 7/21/2026 | DALEH | DALEH | See plans for all comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2336736 |
| Elevators | Original | N | 7/20/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2336624 |
| Zoning/Planning | Original | / | 7/20/2026 | DSDUHLER | DSDUHLER | In Current Review by DSDUHLER | | Zoning/Planning | 2336018 |
| Construction | Original | D | 7/20/2026 | DOUGC | DOUGC | Accessibility // Occupancy // Occ Load * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2336011 |
| Electronic Plan | Original | / | 7/17/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2335741 |
| Enumeration | Original | D | 6/30/2026 | BECKYA | BECKYA | Provide an Architectural Site plan which shows location of all buildings, addressing for all buildings and highlight the scope of work. Enumerations does not approve Civil or Development Plans.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2328821 |
| Electronic Plan | Original | / | 6/30/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2328814 |
| | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/30/2026 for plan submitted 06/30/2026. Submit Date updated to now. Plan now open for review. | | | 2328639 |
| Waste Water Div | Original | / | 6/30/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2328544 |
| Water Division | Original | / | 6/30/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2328543 |
| Energy | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2328542 |
| Floodplain | Original | N | 6/30/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 4220203041) | | Floodplain | 2328541 |