| Fountain Fire | Original | D | 8/6/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | Fountain Fire | 2344581 |
| Fountain Hazmat | Original | D | 8/6/2026 | CSFIRE | CSFIRE | See Fire Comments | phil.valdez | Fountain Hazmat | 2344579 |
| Fountain Zoning | Original | D | 7/27/2026 | ZONINGF | ZONINGF | Plans disapproved pending the review/approval of the site development plan. KM | KMartinez | Fountain Zoning | 2339223 |
| Plumbing | Original | D | 7/24/2026 | SHANEN | SHANEN | Provide plumbing plans that comply with PPRBD plumbing plan review requirements. See link:https://www.pprbd.org/File/ByAlias/PlumbingReview Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. All gas piping related items shall be on the mechanical plans.Remove ALL references to gas piping from the plumbing plans. Provide code path/section that supports discharging a pet wash through an indirect waste connection. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2338799 |
| Energy | Original | D | 7/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2338800 |
| Mechanical | Original | D | 7/22/2026 | DALEH | DALEH | Remove items from floor plan that are located on roof Provide a roof plan Provide a complete gas piping plan Provide condensate routing and size INCOMPLETE REVIEW
See plans for all comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2337815 |
| Electrical | Original | D | 7/22/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11 OR have approved AM&M at time of review
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Provide hazardous location boundary radial dimension on plan
Provide panel demand load in amps
Show compliance with 250.66
Overcurrent proctection required on secondary side of transformer (Panel A)
REVIEW STOPPED. COMPLETE RE-REVIEW WILL BE NESSESSARY * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2337625 |
| Electronic Plan | Original | / | 7/22/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2337381 |
| Elevators | Original | N | 7/22/2026 | STEPHANIEV | STEPHANIEV | NO CONVEYANCES | | Elevators | 2337344 |
| Construction | Original | D | 7/21/2026 | MATTHEWA | MATTHEWA | Code study form // mixed occupancies // Accessibility // Life safety plan // Structural plans // IECC form * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2337259 |
| Electronic Plan | Original | / | 7/16/2026 | MATTHEWA | MATTHEWA | In Current Review by MATTHEWA | | Electronic Plan | 2335377 |
| Enumeration | Original | D | 7/10/2026 | BRENT | BRENT | The address assigned for this parcel is 6131 Sawcut Pt. Update all plan pages and the code study form to show the correct address. The final plat for Mesa Ridge Crossing Fil. No. 3 has not yet been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2333283 |
| Electronic Plan | Original | / | 7/10/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2333268 |
| | Original | / | 7/10/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/10/2026 for plan submitted 06/30/2026. Submit Date updated to now. Plan now open for review. | | | 2333254 |
| Water Division | Original | / | 6/30/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2328551 |
| Waste Water Div | Original | / | 6/30/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2328552 |
| Energy | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2328550 |
| Floodplain | Original | N | 6/30/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5530007004) | | Floodplain | 2328549 |