| Fountain Fire | Original | D | 8/7/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | Fountain Fire | 2344638 |
| Fountain Fire | Original | / | 8/7/2026 | CSFIRE | CSFIRE | | phil.valdez | Fountain Fire | 2344637 |
| Fountain Fire | Original | D | 8/6/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | Fountain Fire | 2344609 |
| Fountain Hazmat | Original | D | 8/6/2026 | CSFIRE | CSFIRE | See Fire Comments | phil.valdez | Fountain Hazmat | 2344604 |
| Fountain Zoning | Original | D | 7/27/2026 | ZONINGF | ZONINGF | Plans disapproved pending review/approval of site development plan. KM | KMartinez | Fountain Zoning | 2339232 |
| Plumbing | Original | D | 7/24/2026 | SHANEN | SHANEN | ST-5 is for residential use only per manufacturer. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. Remove reference to CPC. Water service sizing does not match utility plan. Provide a water heater installation detail to show compliance with 2021 IECC section 404.3 and 2021 IPC section 607.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2339055 |
| Energy | Original | D | 7/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2339056 |
| Mechanical | Original | D | 7/22/2026 | DALEH | DALEH | Provide refrigeration calculations for walk in cooler Walk in cooler must meet 2021 IECC 403.11.2 See plans for complete comments Comcheck must be stamped by design professional
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2337908 |
| Electrical | Original | D | 7/22/2026 | CONNERM | CONNERM | Remove ground from service conductors
Provide AIC and SCA for new air conditioning equipment
Provide a note on the Electrical Plan specifying refrigeration performance per C403.11 and C403.11.3
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.” * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2337355 |
| Electronic Plan | Original | / | 7/22/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2337327 |
| Elevators | Original | N | 7/21/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2336867 |
| Construction | Original | D | 7/21/2026 | JUSTINL | JUSTINL | See code study form, architectural, structural and IECC documents for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2336766 |
| Energy | Original | / | 7/20/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2336437 |
| Electronic Plan | Original | / | 7/17/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2335964 |
| EPC Health Dept | Original | A | 7/8/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. AM | Amanda Furno | EPC Health Dept | 2331782 |
| Enumeration | Original | D | 6/30/2026 | BECKYA | BECKYA | Provide an Architectural Site plan in the Architectural Plans set. Enumerations does not approve Civil or Development Plans * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2328899 |
| Electronic Plan | Original | / | 6/30/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2328896 |
| | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Plan Review fees paid 06/30/2026 for plan submitted 06/30/2026. Submit Date updated to now. Plan now open for review. | | | 2328800 |
| Water Division | Original | / | 6/30/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2328650 |
| Waste Water Div | Original | / | 6/30/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2328651 |
| Energy | Original | / | 6/30/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2328649 |
| Floodplain | Original | N | 6/30/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6513310007) | | Floodplain | 2328648 |