| CO Springs Hazmat | Original | D | 8/10/2026 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2345640 |
| CO Springs Fire | Original | D | 8/10/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | phil.valdez | CO Springs Fire | 2345639 |
| Energy | Original | D | 8/10/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2345311 |
| Mechanical | Original | D | 8/10/2026 | TREVORH | TREVORH | Disapproved; Need to show location of Manual volume and back draft dampers * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2345310 |
| Electrical | Original | D | 8/4/2026 | BERTHA | BERTHA | Pending approval in Enumerations - Multi-meter services must include a list of enumerated addresses on the one-line diagram - Secondary addressing must be approved by Enumerations.
Provide all conductor, size, type and quantity.
Provide all required information for electrical equipment on the one-line - amperage, voltage, etc.
Provide overcurrent protection for MCB and feeders amperage on the one-line
Provide fault current information (SCCR, AIC, SCA) in tabular format at all of the following locations. 1. All new panelboards and switchboards 2. All new transfer equipment 3. All new industrial control panels 4. All new air conditioning and refrigeration equipment 5. At any of the above locations when refed
Clarify amperage of panels.
Provide panel and circuit number on all electrical equipment
Provide information / plans for the scope of work only. Remove all information / plans that does not pertain to this scope of work with the exception of the EV site plan.
Provide a uniform EV site plan for each submittal. The EV site plan must clearly indicate the location and type of EV spot. The EV site plan must indicate at the minimum the same number of spots as indicated on the Development Plan.
Lighting controls must be clearly shown and must comply with C405.2 (Interior), C405.2.7 (Exterior), and C405.2.8 (Parking Garages), where applicable.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Complete re-review necessary.
. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2342758 |
| Plumbing | Original | D | 7/29/2026 | SHANEN | SHANEN | Preliminary review. Construction review comments must be addressed. B occupancy requires compliance with section 403.1. All gas piping related items shall be on the mechanical plans.Remove all references to gas piping from the plumbing plans and provide on the mechanical plans. Provide a piping materials schedule on the plumbing plans per PPRBD plan review requirements. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. See link: https://www.pprbd.org/File/ByAlias/PlumbingReview All plumbing fixtures must be scheduled with manufacturer model numbers per PPRBD commercial plumbing plan review requirements. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Show HWS/HWR on unit plans. Show keynote 15 on all unit plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2340587 |
| Elevators | Original | N | 7/29/2026 | JOHN | JOHN | No elevator in scope of work | | Elevators | 2340551 |
| CO Springs DRE | Original | D | 7/29/2026 | SSADLER | SSADLER | Upload the following documents: the final recorded plat the final approved landscaping and irrigation plans the approval letter
City wide impact fees are due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov | | CO Springs DRE | 2340316 |
| Stormwater | Original | D | 7/27/2026 | JDUNCAN | JDUNCAN | Upload approved SWENT GEC plan. | | Stormwater | 2339625 |
| CSU Contract Admin. | Original | D | 7/23/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal/approval of Commercial Water Meter Sizing Form and payment of development charges/fees. Contact Customer Contract Administration at 719-668-8111. JMD | jdemello | CSU Contract Admin. | 2338575 |
| Zoning/Planning | Original | / | 7/23/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2338307 |
| CSU Water | Original | D | 7/23/2026 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions.
Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans. PSD | PDosch | CSU Water | 2338238 |
| CSU Waste Water | Original | D | 7/23/2026 | CSUREVIEW | CSUREVIEW | Requires CSU-approved wastewater and water mainline Construction Drawings (CD's) and approved Utility Service Plan (USP). Call UDS at 719-668-8259 with questions. PSD | PDosch | CSU Waste Water | 2338236 |
| Gas/Elec. Utils | Original | A | 7/23/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. PSD | PDosch | Gas/Elec. Utils | 2338235 |
| City Engr | Original | D | 7/23/2026 | HVO | HVO | Please upload the approved Street Improvement Plan, and ensure that the Financial Assurance has been paid. | | City Engr | 2338208 |
| Construction | Original | D | 7/23/2026 | JUSTINL | JUSTINL | See code study form, architectural, structural and IECC documents for review comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2338155 |
| Energy | Original | / | 7/21/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2337274 |
| Electronic Plan | Original | / | 7/15/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2334824 |
| Electronic Plan | Original | / | 7/13/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2333734 |
| Floodplain | Original | N | 7/13/2026 | KEITH | KEITH | | | Floodplain | 2333328 |
| Enumeration | Original | D | 7/10/2026 | BECKYA | BECKYA | See page Architectural Plans sheet A1-30 for comments. Final plat for Lakeside Heights at Wolf Ranch Fil. No. 1 has not been recorded. Enumerations approval pending receipt in our office of a copy of the final recorded plat. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2333060 |
| Electronic Plan | Original | / | 7/10/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2333040 |
| | Original | / | 7/9/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/09/2026 for plan submitted 07/01/2026. Submit Date updated to now. Plan now open for review. | | | 2332775 |
| Energy | Original | / | 7/1/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2329494 |