| County Zoning | Original | A | 8/11/2026 | DSDDEAN2 | DSDDEAN2 | Planning and Community Development approved the addition of a restroom and barn renovation on the site at fil no COM2611 no 6/10/2026. Associated Road Impact Fees in the amount of $22,943.15 were paid on 6/4/2026. | | County Zoning | 2346066 |
| Energy | Original | D | 8/10/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2345386 |
| Mechanical | Original | D | 8/10/2026 | TREVORH | TREVORH | Disapproved; Need to Include Refrigeration type in schedule * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2345385 |
| Electrical | Original | D | 8/6/2026 | CONNERM | CONNERM | All new and existing electrical devices must comply with ANSI 117.1 section 308 reach range
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2344176 |
| Electronic Plan | Original | / | 8/6/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2344052 |
| Plumbing | Original | D | 8/6/2026 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. Enumeration comments must be addressed. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. EWC does not comply with section 410.3. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2343972 |
| Elevators | Original | D | 8/5/2026 | ROBERTV | ROBERTV | Need legible site specific Platform Lift drawings to complete review, please upload to 'Elevator Shop Dwgs and Documentation'. Also see sheets: G101, A400, A900, E502, E601 . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2343954 |
| EPC Health Dept | Original | D | 7/24/2026 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. If the entire project is > 1 acre earthmoving, regardless of being submitted in phases and/or separate building permits, a construction activity permit will be required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/construction-land-use/construction-activity-permit/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3.GGM | Heagmiranda | EPC Health Dept | 2339138 |
| Gas/Elec. Utils | Original | A | 7/24/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas meter and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. mjg | mgackle | Gas/Elec. Utils | 2338892 |
| Zoning/Planning | Original | / | 7/24/2026 | DSDDEAN2 | DSDDEAN2 | In Current Review by DSDDEAN2 | | Zoning/Planning | 2338826 |
| Construction | Original | D | 7/24/2026 | SHELLEY | SHELLEY | Code study form, Life safety, rated assemblies, structural. Originally an unpermitted agriculture building, must prove compliance. See plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2338811 |
| Electronic Plan | Original | / | 7/23/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2338043 |
| Enumeration | Original | D | 7/2/2026 | BECKYA | BECKYA | Update all plan pages to show the correct address. The permitted address for the barn is 5208 S Hwy 85-87 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2330308 |
| Floodplain | Original | N | 7/2/2026 | KEITH | KEITH | | | Floodplain | 2330236 |
| Electronic Plan | Original | / | 7/2/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2330147 |
| | Original | / | 7/2/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/02/2026 for plan submitted 07/02/2026. Submit Date updated to now. Plan now open for review. | | | 2330146 |
| Hazmat | Original | / | 7/2/2026 | SYSTEM | SYSTEM | You will need to contact Hazmat department for approval prior to permit. This department will not review the plan electronically. | | Hazmat | 2330138 |
| Fire | Original | / | 7/2/2026 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 2330139 |
| Waste Water Div | Original | / | 7/2/2026 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 2330140 |
| Water Division | Original | / | 7/2/2026 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 2330137 |
| Energy | Original | / | 7/2/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2330136 |
| Floodplain | Original | / | 7/2/2026 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6511300008) | | Floodplain | 2330135 |