| CO Springs Fire | Original | A | 9/9/2026 | CSFIRE | CSFIRE | CSFD FCS: You are responsible for reviewing the comments through your ACA account. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | Jacob.Watson | CO Springs Fire | 2357697 |
| Electrical | Original | A | 9/8/2026 | CONNERM | CONNERM | | | Electrical | 2357137 |
| CO Springs DRE | Original | A | 8/28/2026 | CHUDSPETH | CHUDSPETH | Previous comments still stand from 8/5/2026 | | CO Springs DRE | 2353936 |
| Zoning/Planning | Original | / | 8/27/2026 | CHUDSPETH | CHUDSPETH | In Current Review by CHUDSPETH | | Zoning/Planning | 2353444 |
| Mechanical | Original | A | 8/27/2026 | DALEH | DALEH | | | Mechanical | 2353305 |
| Electrical | Original | D | 8/27/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11 OR have approved AM&M * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2353218 |
| Electronic Plan | Original | / | 8/27/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2353191 |
| Construction | Original | A | 8/27/2026 | JUSTINL | JUSTINL | | | Construction | 2353163 |
| Electronic Plan | Original | / | 8/27/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2353153 |
| Submittal 2 | Original | / | 8/26/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2352724 |
| CO Springs Fire | Original | D | 8/19/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | jt09ff | CO Springs Fire | 2349581 |
| CO Springs Hazmat | Original | N | 8/19/2026 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 2349580 |
| Mechanical | Original | A | 8/5/2026 | DALEH | DALEH | | | Mechanical | 2343619 |
| CO Springs DRE | Original | A | 8/5/2026 | SSADLER | SSADLER | Commercial interior remodel approved. No changes to use, landscaping, footprint, or parking. | | CO Springs DRE | 2343340 |
| Plumbing | Original | A | 8/4/2026 | SHANEN | SHANEN | | | Plumbing | 2342966 |
| Electrical | Original | D | 8/3/2026 | CONNERM | CONNERM | Provide panel and circuit number on all electrical equipment (new and relocated)
Controlled receptacles must be shown on the plan per C405.11 OR have approved AM&M at time of review
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2342526 |
| Electronic Plan | Original | / | 8/3/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2342517 |
| Zoning/Planning | Original | / | 8/3/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2342478 |
| CSU Water | Original | N | 8/3/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2342477 |
| CSU Waste Water | Original | N | 8/3/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2342471 |
| Construction | Original | D | 8/3/2026 | JUSTINL | JUSTINL | See architectural and code study form for review comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2342402 |
| Energy | Original | N | 8/3/2026 | SYSTEM | SYSTEM | Energy Department review not required under 2023 PPRBC when IECC is N/A | | Energy | 2342084 |
| Electronic Plan | Original | / | 8/3/2026 | JUSTINL | JUSTINL | In Current Review by JUSTINL | | Electronic Plan | 2341956 |
| Enumeration | Original | N | 7/28/2026 | BRENT | BRENT | | | Enumeration | 2339826 |
| Electronic Plan | Original | / | 7/28/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2339802 |
| | Original | / | 7/27/2026 | SYSTEM | SYSTEM | Plan Review fees paid 07/27/2026 for plan submitted 07/27/2026. Submit Date updated to now. Plan now open for review. | | | 2339707 |
| Energy | Original | / | 7/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2339624 |
| Floodplain | Original | N | 7/27/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6319205006) | | Floodplain | 2339623 |