| Energy | Original | D | 8/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2349202 |
| Mechanical | Original | A | 8/18/2026 | TCRIPPEN | TCRIPPEN | Approved | | Mechanical | 2349201 |
| Plumbing | Original | D | 8/18/2026 | SHANEN | SHANEN | Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. DWV piping shall be sloped per table 704.1. ST-5 is for residential use only per manufacturer. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. Provide a two way fitting or two riser clean-out at the junction of the building drain and building sewer in compliance with CO state amendment to section 708.1.3. Heated water supply piping must show compliance with 2021 IECC section C404.5.1. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2349023 |
| Electrical | Original | D | 8/18/2026 | DANIELG | DANIELG | Provide the SCA and SCCR for new cooling equipment.
Show size of GEC on grounding detail.
Vestibules must be identified on plans as conditioned or unconditioned. If the vestibule is conditioned or an air curtain is specified, show compliance with C403.4.1.4.
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Comply with the CO MERSRC. CE301.1, CS401.1, CS410.1 and CV501.1
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2349007 |
| Electronic Plan | Original | / | 8/18/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2348983 |
| Elevators | Original | N | 8/18/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2348982 |
| CSU Contract Admin. | Original | D | 8/18/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2348978 |
| City Engr | Original | D | 8/17/2026 | HVO | HVO | Please upload the approved construction drawings for the public street improvements. | | City Engr | 2348764 |
| Stormwater | Original | N | 8/17/2026 | GHUNTLEY | GHUNTLEY | Activity does not disturb an acre or more and is not part of a larger common plan of development. | | Stormwater | 2348476 |
| CO Springs DRE | Original | D | 8/17/2026 | SSADLER | SSADLER | The development plan is still under review. Once approved, upload the approved stamped plans, the final approved landscaping and irrigation plans, and upload the final recorded plat. All fees are due prior to building permit issuance. | | CO Springs DRE | 2348311 |
| Zoning/Planning | Original | / | 8/17/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2348240 |
| CSU Water | Original | D | 8/17/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Water | 2348204 |
| CSU Waste Water | Original | D | 8/17/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | CSU Waste Water | 2348203 |
| Gas/Elec. Utils | Original | D | 8/17/2026 | CSUREVIEW | CSUREVIEW | Approved Development Plan must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. mjg | mgackle | Gas/Elec. Utils | 2348202 |
| Construction | Original | D | 8/14/2026 | BPHILLIPS | BPHILLIPS | Accessibility, CO MERSRC, 1210 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2348110 |
| Electronic Plan | Original | / | 8/13/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2347263 |
| Enumeration | Original | D | 8/13/2026 | AMY | AMY | A wrecking permit need to be in place before Enumerations can approve this plan or any other plan on this lot. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2347129 |
| Electronic Plan | Original | / | 8/13/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2347104 |
| Submittal 2 | Original | / | 8/12/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2346369 |
| Plan Coordinator (Main) | Original | D | 8/5/2026 | AMY | AMY | Disapprove all remaining departments to allow plan to be resubmitted * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plan Coordinator (Main) | 2343697 |
| Enumeration | Original | D | 8/5/2026 | AMY | AMY | Hops & Drops restaurant is already addressed under 5820 Stetson Hills Blvd. Two separate commercial structures cannot have the same address. Please use the address of 5814 Stetson Hills Blvd. Change all pages of the plan to this address.
Code Study form: The legal description and tax schedule number are required to be on the code study form and can be found on the El Paso County Assessor's website under the address to the lot-enter 5820 Stetson Hills Blvd-tax number above the address and legal down below.
The trash enclosure exceeds 7’ therefore, a separate address will need to be assigned along with a separate permit. 1 plan 2 permits will be required. Please use 5816 Stetson Hills Blvd for the enclosure address. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2343696 |
| Electronic Plan | Original | / | 8/5/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2343660 |
| | Original | / | 8/5/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/05/2026 for plan submitted 07/31/2026. Submit Date updated to now. Plan now open for review. | | | 2343542 |
| Energy | Original | / | 7/31/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2341555 |
| Floodplain | Original | N | 7/31/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5318319010) | | Floodplain | 2341554 |