| Energy | Original | D | 8/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2349228 |
| Mechanical | Original | D | 8/18/2026 | TREVORH | TREVORH | Disapproved; Architectural plan submittal is missing the Solar ready zone requirements from the CO MERSRC to accurately determine if roof penetrations will miss the solar panels * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2349227 |
| Electrical | Original | D | 8/18/2026 | CONNERM | CONNERM | Provide fault current info (SCCR, AIC, SCA) for new air conditioning equipment
Controlled receptacles must be shown on the plan per C405.11
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Comply with MERSRC CE302
Comply with MERSRC CS402.6 and CS402.7
Comply with MERSRC CS410.2
Comply with MERSRC CV502 * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2349170 |
| Electronic Plan | Original | / | 8/18/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2349166 |
| Plumbing | Original | D | 8/18/2026 | SHANEN | SHANEN | All gas piping and condensate piping related items shall be on the mechanical plans. Remove ALL references to gas piping and condensate piping from the plumbing plans. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. DF-1 does not comply with section 410.3. CSU approved construction drawings and utility service plan required to verify the plumbing plans correspond with the CSU approved plans for water service sizing, water entry location, building drain sizing, building drain location, etc. 3/4" CW is undersized to serve downstream fixtures. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2349139 |
| Elevators | Original | N | 8/18/2026 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 2349122 |
| Stormwater | Original | D | 8/18/2026 | GHUNTLEY | GHUNTLEY | Missing GEC plan and permit | | Stormwater | 2348952 |
| CO Springs DRE | Original | D | 8/17/2026 | SSADLER | SSADLER | Upload the following documents: final recorded plat final approved landscaping and irrigation plans.
Citywide impact fees are due prior to building permit issuance. Contact Charla at charla.hudspeth@coloradosprings.gov Due to policy changes, assurances for private improvements are now due at C/O | | CO Springs DRE | 2348781 |
| Zoning/Planning | Original | / | 8/17/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2348749 |
| CSU Contract Admin. | Original | D | 8/17/2026 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges and fees. Please contact Customer Contract Administration at 719-668-8111 for additional information on charges/fees and to request an estimate. CWMSF available online at:
https://www.csu.org/CSUDocuments/watermetersizingforminteractive.pdf
AMS | ASweet | CSU Contract Admin. | 2348731 |
| CSU Water | Original | D | 8/17/2026 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
Refer to the current Colorado Springs Utilities WaterLESS details B4-1 through B4-8 and select the correct meter detail to include on the plumbing plans after approval of the Commercial Water Meter Sizing Form. Also refer to details B4-16 through B4-22 and select an appropriate meter clearance detail to include on the plumbing plans.
At building connection, the water service line size shown on the Plumbing drawings does not currently match the Utility Service Plan drawings. SSH | SHillman | CSU Water | 2348657 |
| CSU Waste Water | Original | D | 8/17/2026 | CSUREVIEW | CSUREVIEW | CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions.
At building connection, the sanitary service line size shown on the Plumbing drawings does not currently match the Utility Service Plan drawings. SSH | SHillman | CSU Waste Water | 2348653 |
| Gas/Elec. Utils | Original | A | 8/17/2026 | CSUREVIEW | CSUREVIEW | CSU Field Engineer to determine final gas/electric meter, transformer and service line locations. Contact Field Engineering at 719-668-4985 (Gas) or 719-668-5564 (Electric) with any questions. SSH | SHillman | Gas/Elec. Utils | 2348651 |
| City Engr | Original | D | 8/17/2026 | HVO | HVO | Please upload the approved construction drawings for the public street improvements. | | City Engr | 2348584 |
| Construction | Original | D | 8/17/2026 | DOUGC | DOUGC | CSF // Architectural // Structural * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2348537 |
| Electronic Plan | Original | / | 8/17/2026 | DOUGC | DOUGC | In Current Review by DOUGC | | Electronic Plan | 2348409 |
| Enumeration | Original | D | 8/17/2026 | BECKYA | BECKYA | 1. The address for the office will not need a letter. Remove Building I from all plan pages. 2. Fence and Trash Enclosure are under 7’ in height and will not require a separate address or permit. 3. The final plat for Old Ranch Storage Filing No. 1 was not provided to Enumerations for review. Please have the planner with the City of Colorado Springs add us to the review for SUBD-26-0016. Any plans submitted for this project will not be approved until plat fees have been paid and the final plat has been recorded and sent to us for our records. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2348276 |
| Electronic Plan | Original | / | 8/14/2026 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 2347978 |
| | Original | / | 8/14/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/14/2026 for plan submitted 08/14/2026. Submit Date updated to now. Plan now open for review. | | | 2347799 |
| Energy | Original | / | 8/14/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2347744 |
| Floodplain | Original | N | 8/14/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6222300007) | | Floodplain | 2347742 |