| CO Springs Hazmat | Original | N | 9/4/2026 | CSFIRE | CSFIRE | | phil.valdez | CO Springs Hazmat | 2356867 |
| Energy | Original | D | 8/31/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2354477 |
| Mechanical | Original | D | 8/31/2026 | TREVORH | TREVORH | Disapproved; Mechanical pending Elevator approval. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2354476 |
| Electrical | Original | D | 8/27/2026 | BERTHA | BERTHA | Provide elevator horsepower on the one line.
Provide SCCR and SCA at/for the Elevator controller.
Provide elevator feeder size, type, and quantity on the one line.
Provide elevator over current device size ( Ampacity) on the one line.
Pending Elevator plan review approval/release. . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2353375 |
| Plumbing | Original | D | 8/27/2026 | SHANEN | SHANEN | Elevator review comments must be addressed. Elevator sump discharge shall comply with section 301.6 Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the shaft, provided that they are indirectly connected to the plumbing system. Discharge elevator sump indirectly to a waste receptor capable of handling a minimum of 50 gpm (100 dfu). * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2353172 |
| Elevators | Original | D | 8/27/2026 | ROBERTV | ROBERTV | Need site specific shop drawings, power data and controller short circuit current rating (SCCR) for all elevators being installed. All elevator shop drawing and power data information must be situated in all of the required pages of this planset to include all work by others. Dimensions, notes and layouts must match in all trade pages. These submittals cannot be deferred and cannot use Basis of Design. Without these, a review cannot be performed and will continue to be disapproved.
Also see sheets: CS, A1, A2, S1, S2, E1, E2, P2
Where is the Mechanical Sheets showing the Ventilation / HVAC requirements for the elevator machine room ? . * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Elevators | 2353131 |
| City Engr | Original | A | 8/27/2026 | DSOSA | DSOSA | EDRD has no comments | | City Engr | 2353104 |
| CO Springs DRE | Original | A | 8/27/2026 | SSADLER | SSADLER | Approved for an elevator addition. | | CO Springs DRE | 2352830 |
| Zoning/Planning | Original | / | 8/26/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2352194 |
| EPC Health Dept | Original | A | 8/25/2026 | HEALTHDEPT | HEALTHDEPT | Not applicable. Elevator addition and deck/exterior remodel only. AB | abrannon | EPC Health Dept | 2351902 |
| Gas/Elec. Utils | Original | N | 8/25/2026 | CSUREVIEW | CSUREVIEW | | jsnoel | Gas/Elec. Utils | 2351868 |
| CSU Waste Water | Original | N | 8/25/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MDA | malcuran | CSU Waste Water | 2351750 |
| CSU Water | Original | N | 8/25/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building.MDA | malcuran | CSU Water | 2351736 |
| Electronic Plan | Original | / | 8/25/2026 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 2351725 |
| Construction | Original | A | 8/25/2026 | JUSTINL | JUSTINL | | | Construction | 2351713 |
| Enumeration | Original | N | 8/25/2026 | BRENT | BRENT | | | Enumeration | 2351680 |
| Electronic Plan | Original | / | 8/25/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2351670 |
| | Original | / | 8/24/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/24/2026 for plan submitted 08/24/2026. Submit Date updated to now. Plan now open for review. | | | 2351373 |
| Energy | Original | / | 8/24/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2351194 |
| Floodplain | Original | N | 8/24/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6307003005) | | Floodplain | 2351193 |