| CO Springs Fire | Original | D | 9/8/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | Jacob.Watson | CO Springs Fire | 2357301 |
| CO Springs Hazmat | Original | N | 9/8/2026 | CSFIRE | CSFIRE | NA | Jacob.Watson | CO Springs Hazmat | 2357297 |
| Energy | Original | D | 9/2/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2355742 |
| Mechanical | Original | A | 9/2/2026 | DALEH | DALEH | | | Mechanical | 2355741 |
| CO Springs DRE | Original | A | 9/1/2026 | SSADLER | SSADLER | Approved for the addition of a new accessible restroom. No changes to existing footprint, parking, landscaping, or use | | CO Springs DRE | 2354604 |
| Enumeration | Original | A | 8/28/2026 | AMY | AMY | Interior remodel to create new suite 2410 S Academy Blvd suite 120. The address was correct on all sheets. If any sheet gets changed out correct the address. | | Enumeration | 2353636 |
| Construction | Original | D | 8/28/2026 | SHELLEY | SHELLEY | See plans for issues * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2353629 |
| Energy | Original | / | 8/28/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2353628 |
| Zoning/Planning | Original | / | 8/28/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2353504 |
| CSU Water | Original | N | 8/27/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2353478 |
| CSU Waste Water | Original | N | 8/27/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. PSD | PDosch | CSU Waste Water | 2353477 |
| Plumbing | Original | D | 8/27/2026 | SHANEN | SHANEN | Construction review comments must be addressed to verify compliance with section 403.1. Lavatories must show compliance with 2021 IECC section C404.5.1. Provide drinking fountain shown on the architectural plans. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2353415 |
| Electrical | Original | D | 8/27/2026 | DANIELG | DANIELG | Pending construction review. Electrical is ok. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2353410 |
| Floodplain | Original | N | 8/27/2026 | BECKYA | BECKYA | | | Floodplain | 2353405 |
| Enumeration | Original | D | 8/27/2026 | AMY | AMY | This space is not large enough to be 2 suites. Provide more information as Construction has requested to be able to move forward. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2353403 |
| Construction | Original | D | 8/27/2026 | SHELLEY | SHELLEY | Need to verify suite. Suite 2412 is not large enough to have been split in two. It appears work has been done without permits. Contractor to verify location. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2353398 |
| Electrical | Original | A | 8/27/2026 | DANIELG | DANIELG | | | Electrical | 2353393 |
| Electronic Plan | Original | / | 8/27/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2353371 |
| | Original | / | 8/27/2026 | SYSTEM | SYSTEM | Plan Review fees paid 08/27/2026 for plan submitted 08/27/2026. Submit Date updated to now. Plan now open for review. | | | 2353297 |
| Energy | Original | / | 8/27/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2353292 |
| Floodplain | Original | / | 8/27/2026 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6427419004) | | Floodplain | 2353291 |