| CSU Gas | Original | A | 9/28/2026 | CSUREVIEW | CSUREVIEW | No apparent conflicts.jl | jluukkonen | CSU Gas | 2364486 |
| Stormwater | Original | N | 9/28/2026 | GHUNTLEY | GHUNTLEY | Interior finish, does not require SWENT | | Stormwater | 2364421 |
| City Engr | Original | N | 9/28/2026 | HVO | HVO | | | City Engr | 2364372 |
| EPC Health Dept | Original | D | 9/28/2026 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/licenses-permits-inspections-water-testing/retail-food/retail-food-establishments/. Please submit all applications through https://myhealthdepartment.com/EPCPH. For questions, contact Environmental Health at 719-578-3199 option 3. KB. | KBauer | EPC Health Dept | 2364282 |
| CSU Contract Admin. | Original | N | 9/28/2026 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved and applicable development fees/charges paid - master meter configuration. AMS | ASweet | CSU Contract Admin. | 2364234 |
| CSU Waste Water | Original | N | 9/28/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. Connection to existing 1500 gallon grease interceptor. PSD | PDosch | CSU Waste Water | 2364199 |
| CSU Water | Original | N | 9/28/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. PSD | PDosch | CSU Water | 2364197 |
| CSU Electric | Original | D | 9/28/2026 | CSUREVIEW | CSUREVIEW | Submit Electric Load Data Form to CSU Field Engineering. Form can be found at: https://www.csu.org/hubfs/Document-Library/ElectricLoadData.pdf?hsLang=en
JF | JulianFoster | CSU Electric | 2364166 |
| Plumbing | Original | D | 9/28/2026 | SHANEN | SHANEN | Provide project address on all plumbing drawings. Provided water pipe size analysis data is incomplete. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. All applicable data may be calculated from the point of connection. Drainage piping shall be sloped per table 704.1. Provide a piping insulation materials schedule, code tables are not an acceptable substitute. Piping insulation material schedule must include thickness, material (fiberglass, elastomeric foam, etc.) and manufacturer. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2364136 |
| Electrical | Original | D | 9/28/2026 | DANIELG | DANIELG | Comply with the CO MERSRC CE301.1
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
See one-line for comments.
* Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2364110 |
| Zoning/Planning | Original | / | 9/28/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2364098 |
| Electronic Plan | Original | / | 9/28/2026 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 2364095 |
| Construction | Original | D | 9/28/2026 | BPHILLIPS | BPHILLIPS | Specify egress width requirements for all exit elements. Show accessible entrances and exits (as applicable).Indicate location of common path of travel. Restroom elevations. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2364089 |
| Electronic Plan | Original | / | 9/25/2026 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 2363546 |
| Enumeration | Original | D | 9/21/2026 | AMY | AMY | Plan checked in under the address of 100 E Cheyenne Road, Code Study form shows 110 E Cheyenne Road. Correct this address along with the suite number. This is lot 2 not lot 3, correct this on the Code Study form. The floor plan G0001 has been corrected to show the currant suite numbers based on permit history. This suite number is #120, not 130. Change the suite number on all pages of this plan, even if there is an approval stamp from another department. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Enumeration | 2361415 |
| Electronic Plan | Original | / | 9/21/2026 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 2361400 |
| | Original | / | 9/18/2026 | SYSTEM | SYSTEM | Plan Review fees paid 09/18/2026 for plan submitted 09/18/2026. Submit Date updated to now. Plan now open for review. | | | 2361210 |
| Energy | Original | / | 9/18/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2361182 |
| Floodplain | Original | N | 9/18/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6430213030) | | Floodplain | 2361181 |