| Zoning/Planning | Original | / | 10/20/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2372793 |
| Electrical | Original | D | 10/19/2026 | CONNERM | CONNERM | Comply with previous comments.
Missing panel schedule and power plan. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2372702 |
| Electronic Plan | Original | / | 10/19/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2372670 |
| Plumbing | Original | A | 10/19/2026 | SHANEN | SHANEN | | | Plumbing | 2372591 |
| Construction | Original | D | 10/19/2026 | SHELLEY | SHELLEY | Still missing IECC form * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2372548 |
| Enumeration | Original | A | 10/19/2026 | BRENT | BRENT | | | Enumeration | 2372412 |
| Electronic Plan | Original | / | 10/19/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2372407 |
| Submittal 2 | Original | / | 10/19/2026 | MELISSAF | MELISSAF | Submittal #2 | | Submittal 2 | 2372324 |
| CO Springs Fire | Original | D | 10/14/2026 | CSFIRE | CSFIRE | You must have a ACA account in order to view your disapproval comments. You can find the link to the ACA website and a tutorial video on how to set up an account at: https://coloradosprings.gov/fire-code-resources . If you do not have an ACA account at time of CSFD review you will need to reach out to the CSFD Construction Service staff to link the review to your account. | chiptaylor | CO Springs Fire | 2370761 |
| CO Springs Hazmat | Original | N | 10/14/2026 | CSFIRE | CSFIRE | | chiptaylor | CO Springs Hazmat | 2370758 |
| CO Springs DRE | Original | D | 10/9/2026 | SSADLER | SSADLER | Give a description of the business type | | CO Springs DRE | 2369275 |
| Energy | Original | D | 10/8/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2368680 |
| Mechanical | Original | D | 10/8/2026 | DALEH | DALEH | See mechanical sheets for all comments * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Mechanical | 2368679 |
| CSU Water | Original | N | 10/7/2026 | CSUREVIEW | CSUREVIEW | No new water service outside of building. SSH | SHillman | CSU Water | 2368363 |
| CSU Waste Water | Original | N | 10/7/2026 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. SSH | SHillman | CSU Waste Water | 2368361 |
| Electronic Plan | Original | / | 10/7/2026 | QUINTONW | QUINTONW | In Current Review by QUINTONW | | Electronic Plan | 2368277 |
| Plumbing | Original | D | 10/7/2026 | SHANEN | SHANEN | Construction review comments regarding occupant load must be addressed to verify compliance with section 403.1. Compliance with 2021 IPC and CO state amendments to 2021 IPC must be stated on the plumbing plans. Construction review comments regarding clear floor space must be addressed as backgrounds may change. Provide required water pipe size analysis data, see 2021 IPC appendix E. Data must include: service pressure, service size, meter size, pressure loss, available pressure, distribution size, WSFU served, developed length, etc. Show compliance with commercial plumbing plan review additional requirements for 2021 IECC. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Plumbing | 2368183 |
| Electrical | Original | D | 10/7/2026 | CONNERM | CONNERM | Controlled receptacles must be shown on the plan per C405.11 OR have approved AM&M
Provide a note on the plans indicating that the Electrical design has a maximum volt drop of 5% per C405.10.
The following general note must be included on the electrical plans: “A Final Commissioning Report shall be delivered to the building owner per section C408.2.5 of the 2021 IECC.”
Clarify panel as new or existing. Provide one line * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Electrical | 2368136 |
| Zoning/Planning | Original | / | 10/7/2026 | SSADLER | SSADLER | In Current Review by SSADLER | | Zoning/Planning | 2368125 |
| Electronic Plan | Original | / | 10/7/2026 | CONNERM | CONNERM | In Current Review by CONNERM | | Electronic Plan | 2368119 |
| Construction | Original | D | 10/7/2026 | SHELLEY | SHELLEY | IECC, occupant load, scale, duplicate sheets, accessibility, see plans for all comments. * Please see either the "Progress Set" or the "Review Set" for complete list of this department's corrections. Plans cannot be re-submitted until all required departments have completed their review. * | | Construction | 2368098 |
| Electronic Plan | Original | / | 10/6/2026 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Electronic Plan | 2367403 |
| Enumeration | Original | A | 10/2/2026 | BRENT | BRENT | | | Enumeration | 2366363 |
| Electronic Plan | Original | / | 10/2/2026 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 2366356 |
| | Original | / | 10/1/2026 | SYSTEM | SYSTEM | Plan Review fees paid 10/01/2026 for plan submitted 10/01/2026. Submit Date updated to now. Plan now open for review. | | | 2366188 |
| Energy | Original | / | 10/1/2026 | SYSTEM | SYSTEM | Energy Department review for 2023 PPRBC is based on status of Construction, Electrical, Mechanical and Plumbing reviews | | Energy | 2366183 |
| Floodplain | Original | N | 10/1/2026 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233201014) | | Floodplain | 2366182 |